Regulation 10 - Fire fighting
1 Purpose
1.1 The purpose of this regulation is to suppress and
swiftly extinguish a fire in the space of origin, except for paragraph 1.2. For this
purpose, the following functional requirements shall be met:
1.2 For open-top container holdsfootnote and on deck container stowage areas on ships designed to carry
containers on or above the weather deck, constructed on or after 1 January 2016, fire
protection arrangements shall be provided for the purpose of containing a fire in the
space or area of origin and cooling adjacent areas to prevent fire spread and
structural damage.
2 Water supply systems
Ships shall be provided with fire pumps, fire mains, hydrants
and hoses complying with the applicable requirements of this regulation.
2.1 Fire mains and
hydrant
Materials readily rendered ineffective by heat shall not
be used for fire mains and hydrants unless adequately protected. The
pipes and hydrants shall be so placed that the fire hoses may be easily
coupled to them. The arrangement of pipes and hydrants shall be such
as to avoid the possibility of freezing. Suitable drainage provisions
shall be provided for fire main piping. Isolation valves shall be
installed for all open deck fire main branches used for purposes other
than fire fighting. In ships where deck cargo may be carried, the
positions of the hydrants shall be such that they are always readily
accessible and the pipes shall be arranged as far as practicable to
avoid risk of damage by such cargo.
2.1.2
Ready availability of water supply
The arrangements for the ready availability of water supply
shall be:
-
.1 in passenger ships:
-
.1.1 of 1,000 gross tonnage and upwards such that
at least one effective jet of water is immediately available from
any hydrant in an interior location and so as to ensure the continuation
of the output of water by the automatic starting of one required fire
pump;
-
.1.2 of less than 1,000 gross tonnage by automatic
start of at least one fire pump or by remote starting from the navigation
bridge of at least one fire pump. If the pump starts automatically
or if the bottom valve cannot be opened from where the pump is remotely
started, the bottom valve shall always be kept open; and
-
.1.3 if fitted with periodically unattended machinery
spaces in accordance with regulation
II-1/54, the Administration shall determine provisions for
fixed water fire-extinguishing arrangement for such spaces equivalent
to those required for normally attended machinery spaces;
-
.2 in cargo ships:
-
.2.1 to the satisfaction of the Administration;
and
-
.2.2 with a periodically unattended machinery
space or when only one person is required on watch, there shall be
immediate water delivery from the fire main system at a suitable pressure,
either by remote starting of one of the main fire pumps with remote
starting from the navigating bridge and fire control station, if any,
or permanent pressurization of the fire main system by one of the
main fire pumps, except that the Administration may waive this requirement
for cargo ships of less than 1,600 gross tonnage if the fire pump
starting arrangement in the machinery space is in an easily accessible
position.
2.1.3
Diameter of fire mains
The diameter of the fire main and water service pipes shall be
sufficient for the effective distribution of the maximum required discharge from
two fire pumps operating simultaneously, except that in the case of cargo ships,
other than those included in paragraph 7.3.2, the diameter need only be sufficient
for the discharge of 140 m3/h.
2.1.4
Isolating valves and relief valves
2.1.4.1 Isolating valves to separate the section
of the fire main within the machinery space containing the main fire
pump or pumps from the rest of the fire main shall be fitted in an
easily accessible and tenable position outside the machinery spaces.
The fire main shall be so arranged that when the isolating valves
are shut all the hydrants on the ship, except those in the machinery
space referred to above, can be supplied with water by another fire
pump or an emergency fire pump. The emergency fire pump, its seawater
inlet, and suction and delivery pipes and isolating valves shall be
located outside the machinery space. If this arrangement cannot be
made, the sea-chest may be fitted in the machinery space if the valve
is remotely controlled from a position in the same compartment as
the emergency fire pump and the suction pipe is as short as practicable.
Short lengths of suction or discharge piping may penetrate the machinery
space, provided they are enclosed in a substantial steel casing, or
are insulated to "A-60" class standards. The pipes shall have substantial
wall thickness, but in no case less than 11 mm, and shall be welded
except for the flanged connection to the sea inlet valve.
2.1.4.2 A valve shall be fitted to serve each
fire hydrant so that any fire hose may be removed while the fire pumps
are in operation.
2.1.4.3 Relief valves shall be provided in conjunction
with fire pumps if the pumps are capable of developing a pressure
exceeding the design pressure of the water service pipes, hydrants
and hoses. These valves shall be so placed and adjusted as to prevent
excessive pressure in any part of the fire main system.
2.1.4.4 In tankers, isolation valves shall be
fitted in the fire main at poop front in a protected position and
on the tank deck at intervals of not more than 40 m to preserve the
integrity of the fire main system in case of fire or explosion.
2.1.5
Number and position of hydrants
2.1.5.1 The number and position of hydrants shall
be such that at least two jets of water not emanating from the same
hydrant, one of which shall be from a single length of hose, may reach
any part of the ship normally accessible to the passengers or crew
while the ship is being navigated and any part of any cargo space
when empty, any ro-ro space or any vehicle space in which latter case
the two jets shall reach any part of the space, each from a single
length of hose. Furthermore, such hydrants shall be positioned near
the accesses to the protected spaces.
2.1.5.2 In addition to the requirements in the
paragraph 2.1.5.1, passenger ships shall comply with the following:
-
.1 in the accommodation, service and machinery
spaces the number and position of hydrants shall be such that the
requirements of paragraph 2.1.5.1 may be complied with when all watertight
doors and all doors in main vertical zone bulkheads are closed; and
-
.2 where access is provided to a machinery space
of category A at a low level from an adjacent shaft tunnel, two hydrants
shall be provided external to, but near the entrance to that machinery
space. Where such access is provided from other spaces, in one of
those spaces two hydrants shall be provided near the entrance to the
machinery space of category A. Such provision need not be made where
the tunnel or adjacent spaces are not part of the escape route.
2.1.6
Pressure at hydrants
With the two pumps simultaneously delivering water through
the nozzles specified in paragraph
2.3.3, with the quantity of water as specified in paragraph 2.1.3, through any adjacent
hydrants, the following minimum pressures shall be maintained at all
hydrants:
.1
|
for
passenger ships:
|
|
|
4,000 gross tonnage and
upwards
|
0.40
N/mm2
|
|
less than 4,000 gross
tonnage
|
0.30
N/mm2
|
.2
|
for cargo ships:
|
|
|
6,000 gross tonnage and
upwards
|
0.27
N/mm2
|
|
less than 6,000 gross
tonnage; and
|
0.25
N/mm2
|
.3
|
the maximum pressure
at any hydrant shall not exceed that at which the effective control
of a fire hose can be demonstrated.
|
2.1.7
International shore connection
2.1.7.1 Ships of 500 gross tonnage and upwards
shall be provided with at least one international shore connection
complying with the Fire Safety Systems Code.
2.1.7.2 Facilities shall be available enabling
such a connection to be used on either side of the ship.
2.2 Fire pumps
2.2.1
Pumps accepted as fire pumps
Sanitary, ballast, bilge or general service pumps may be
accepted as fire pumps, provided that they are not normally used for
pumping oil and that if they are subject to occasional duty for the
transfer or pumping of oil fuel, suitable change-over arrangements
are fitted.
2.2.2
Number of fire pumps
Ships shall be provided with independently driven
fire pumps as follows:
.1
|
in
passenger ships of:
|
|
|
4,000 gross tonnage and
upwards
|
at
least three
|
|
less that 4,000 gross
tonnage
|
at
least two
|
.2
|
for cargo ships of:
|
|
|
1,000 gross tonnage and
upwards
|
at
least two
|
|
less than 1,000 gross
tonnage
|
at
least two power driven pumps, one of which shall be independently
driven.
|
2.2.3
Arrangement of fire pumps and fire
mains
The arrangement of sea connections, fire pumps and their
sources of power shall be as to ensure that:
-
.1 in passenger ships of l,000 gross tonnage and
upwards, in the event of a fire in any one compartment all the fire
pumps will not be put out of action; and
-
.2 in passenger ships of less than 1,000 gross
tonnage and in cargo ships, if a fire in any one compartment could
put all the pumps out of action, there shall be an alternative means
consisting of an emergency fire pump complying with the provisions
of the Fire Safety Systems Code with its source of power and sea connection
located outside the space where the main fire pumps or their sources
of power are located.
2.2.3.2
Requirements for the space containing
the emergency fire pump
2.2.3.2.1
Location of the space
The space containing the fire pump shall not be contiguous
to the boundaries of machinery spaces of category A or those spaces
containing main fire pumps. Where this is not practicable, the common
bulkhead between the two spaces shall be insulated to a standard of
structural fire protection equivalent to that required for a control
station.
2.2.3.2.2
Access to the emergency fire pump
No direct access shall be permitted between the machinery
space and the space containing the emergency fire pump and its source
of power. When this is impracticable, the Administration may accept
an arrangement where the access is by means of an airlock with the
door of the machinery space being of "A-60" class standard, and the
other door being at least steel, both reasonably gastight, self-closing
and without any hold-back arrangements. Alternatively, the access
may be through a watertight door capable of being operated from a
space remote from the machinery space and the space containing the
emergency fire pump and unlikely to be cut off in the event of fire
in those spaces. In such cases, a second means of access to the space
containing the emergency fire pump and its source of power shall be
provided.
2.2.3.2.3
Ventilation of the emergency fire
pump space
Ventilation arrangements to the space containing the independent
source of power for the emergency fire pump shall be such as to preclude,
as far as practicable, the possibility of smoke from a machinery space
fire entering or being drawn into that space.
2.2.3.3
Additional pumps for cargo ships
In addition, in cargo ships where other pumps, such as general
service, bilge and ballast, etc., are fitted in a machinery space,
arrangements shall be made to ensure that at least one of these pumps,
having the capacity and pressure required by paragraphs 2.1.6.2 and 2.2.4.2, is capable of providing
water to the fire main.
2.2.4
Capacity of fire pumps
2.2.4.1
Total capacity of required fire
pumps
The required fire pumps shall be capable of delivering for
fire-fighting purposes a quantity of water, at the pressure specified
in paragraph 2.1.6, as follows:
-
.1 pumps in passenger ships: the quantity of
water is not less than two thirds of the quantity required to be dealt
with by the bilge pumps when employed for bilge pumping; and
-
.2 pumps in cargo ships, other than any
emergency pump: the quantity of water is not less than four thirds of the
quantity required under regulation
II-1/35–1 to be dealt with by each of the independent bilge pumps
in a passenger ship of the same dimension when employed in bilge pumping,
provided that in no cargo ship, other than those included in paragraph
7.3.2, need the total required capacity of the fire pumps exceed 180
m3/h.
2.2.4.2
Capacity of each fire pump
Each of the required fire pumps (other than any emergency
pump required in paragraph 2.2.3.1.2 for
cargo ships) shall have a capacity not less than 80% of the total
required capacity divided by the minimum number of required fire pumps
but in any case not less than 25 m3/h and each such pump
shall in any event be capable of delivering at least the two required
jets of water. These fire pumps shall be capable of supplying the
fire main system under the required conditions. Where more pumps than
the minimum of required pumps are installed such additional pumps
shall have a capacity of at least 25 m3/h and shall be
capable of delivering at least the two jets of water required in paragraph 2.1.5.1.
2.3 Fire hoses and
nozzles
2.3.1
General specifications
2.3.1.1 Fire hoses shall be of non-perishable
material approved by the Administration and shall be sufficient in
length to project a jet of water to any of the spaces in which they
may be required to be used. Each hose shall be provided with a nozzle
and the necessary couplings. Hoses specified in this chapter as "fire
hoses" shall, together with any necessary fittings and tools, be kept
ready for use in conspicuous positions near the water service hydrants
or connections. Additionally, in interior locations in passenger ships
carrying more than 36 passengers fire hoses shall be connected to
the hydrants at all times. Fire hoses shall have a length of at least
10 m, but not more than:
-
.1 15 m in machinery spaces;
-
.2 20 m in other spaces and open decks; and
-
.3 25 m for open decks on ships with a maximum
breadth in excess of 30 m.
2.3.1.2 Unless one hose and nozzle is provided
for each hydrant in the ship, there shall be complete interchangeability
of hose couplings and nozzles.
2.3.2
Number and diameter of fire hoses
2.3.2.1 Ships shall be provided with fire hoses
the number and diameter of which shall be to the satisfaction of the
Administration.
2.3.2.2 In passenger ships, there shall be at
least one fire hose for each of the hydrants required by paragraph 2.1.5 and these hoses
shall be used only for the purposes of extinguishing fires or testing
the fire-extinguishing apparatus at fire drills and surveys.
2.3.2.3 In cargo ships:
-
.1 of 1,000 gross tonnage and upwards, the number
of fire hoses to be provided shall be one for each 30 m length of
the ship and one spare but in no case less than five in all. This
number does not include any hoses required in any engine or boiler
room. The Administration may increase the number of hoses required
so as to ensure that hoses in sufficient number are available and
accessible at all times, having regard to the type of ship and the
nature of trade in which the ship is employed. Ships carrying dangerous
goods in accordance with regulation
19 shall be provided with 3 hoses and nozzles, in addition
to those required above; and
-
.2 of less than 1,000 gross tonnage, the number
of fire hoses to be provided shall be calculated in accordance with
the provisions of paragraph 2.3.2.3.1.
However, the number of hoses shall in no case be less than three.
2.3.3
Size and types of nozzles
2.3.3.1 For the purposes of this chapter, standard
nozzle sizes shall be 12 mm, 16 mm and 19 mm or as near thereto as
possible. Larger diameter nozzles may be permitted at the discretion
of the Administration.
2.3.3.2 For accommodation and service spaces,
a nozzle size greater than 12 mm need not be used.
2.3.3.3 For machinery spaces and exterior locations,
the nozzle size shall be such as to obtain the maximum discharge possible
from two jets at the pressure mentioned in paragraph 2.1.6 from the smallest
pump, provided that a nozzle size greater than 19 mm need not be used.
2.3.3.4 Nozzles shall be of an approved dual-purpose
type (i.e., spray/jet type) incorporating a shutoff.
3 Portable fire extinguishers
footnote
Portable fire extinguishers shall comply with the requirements
of the Fire Safety Systems Code.
3.2
Arrangement of fire extinguishers
3.2.1 Accommodation spaces, service spaces and
control stations shall be provided with portable fire extinguishers
of appropriate types and in sufficient number to the satisfaction
of the Administration. Ships of 1,000 gross tonnage and upwards shall
carry at least five portable fire extinguishers.
3.2.2 One of the portable fire extinguishers intended
for use in any space shall be stowed near the entrance to that space.
3.2.3 Carbon dioxide fire extinguishers shall
not be placed in accommodation spaces. In control stations and other
spaces containing electrical or electronic equipment or appliances
necessary for the safety of the ship, fire extinguishers should be
provided whose extinguishing media are neither electrically conductive
nor harmful to the equipment and appliances.
3.2.4 Fire extinguishers shall be situated ready
for use at easily visible places, which can be reached quickly and
easily at any time in the event of a fire, and in such a way that
their serviceability is not impaired by the weather, vibration or
other external factors. Portable fire extinguishers shall be provided
with devices which indicate whether they have been used.
3.3.1 Spare charges shall be provided for 100%
of the first 10 extinguishers and 50% of the remaining fire extinguishers
capable of being recharged on board. Not more than 60 total spare
charges are required. Instructions for recharging shall be carried
on board.
3.3.2 For fire extinguishers which cannot be recharged
on board, additional portable fire extinguishers of the same quantity,
type, capacity and number as determined in paragraph 3.3.1 above shall be provided
in lieu of spare charges.
4 Fixed fire-extinguishing
systems
4.1
Types of fixed fire-extinguishing systems
4.1.1 A fixed fire-extinguishing system required
by paragraph 5 below may be
any of the following systems:
-
.1 a fixed gas fire-extinguishing system complying
with the provisions of the Fire Safety Systems Code;
-
.2 a fixed high-expansion foam fire-extinguishing
system complying with the provisions of the Fire Safety Systems Code;
and
-
.3 a fixed pressure water-spraying fire-extinguishing
system complying with the provisions of the Fire Safety Systems Code.
4.1.2 Where a fixed fire-extinguishing system
not required by this chapter is installed, it shall meet the requirements
of the relevant regulations of this chapter and the Fire Safety Systems
Code.
4.1.3 Fire-extinguishing systems using Halon 1211,
1301, and 2402 and perfluorocarbons shall be prohibited.
4.1.4 In general, the Administration shall not
permit the use of steam as a fire-extinguishing medium in fixed fire-extinguishing
systems. Where the use of steam is permitted by the Administration,
it shall be used only in restricted areas as an addition to the required
fire-extinguishing system and shall comply with the requirements of
the Fire Safety Systems Code.
4.1.5 By the first scheduled dry-docking after
1 January 2010, fixed carbon dioxide fire-extinguishing systems for
the protection of machinery spaces and cargo pump-rooms on ships constructed
before 1 July 2002 shall comply with the provisions of paragraph 2.2.2
of chapter 5 of the Fire Safety Systems
Code.
4.2
Closing appliances for fixed gas fire-extinguishing
systems
Where a fixed gas fire-extinguishing system is used, openings
which may admit air to, or allow gas to escape from, a protected space
shall be capable of being closed from outside the protected space.
4.3
Storage rooms of fire-extinguishing
medium
When the fire-extinguishing medium is stored outside a protected
space, it shall be stored in a room which is located behind the forward
collision bulkhead, and is used for no other purposes. Any entrance
to such a storage room shall preferably be from the open deck and
shall be independent of the protected space. If the storage space
is located below deck, it shall be located no more than one deck below
the open deck and shall be directly accessible by a stairway or ladder
from the open deck. Spaces which are located below deck or spaces
where access from the open deck is not provided, shall be fitted with
a mechanical ventilation system designed to take exhaust air from
the bottom of the space and shall be sized to provide at least 6 air
changes per hour. Access doors shall open outwards, and bulkheads
and decks including doors and other means of closing any opening therein,
which form the boundaries between such rooms and adjacent enclosed
spaces shall be gastight. For the purpose of the application of tables 9.1 to 9.8, such storage rooms
shall be treated as fire control stations.
4.4
Water pumps for other fire-extinguishing
systems
Pumps, other than those serving the fire main, required
for the provision of water for fire-extinguishing systems required
by this chapter, their sources of power and their controls shall be
installed outside the space or spaces protected by such systems and
shall be so arranged that a fire in the space or spaces protected
will not put any such system out of action.
5 Fire extinguishing
arrangements in machinery spaces
5.1
Machinery spaces containing
oil-fired boilers or oil fuel units
5.1.1
Fixed fire-extinguishing
systems
Machinery spaces of category A containing oil-fired
boilers or oil fuel units shall be provided with any one of the fixed
fire-extinguishing systems in paragraph
4.1. In each case, if the engine and boiler rooms are not entirely
separate, or if fuel oil can drain from the boiler room into the engine-room,
the combined engine and boiler rooms shall be considered as one compartment.
5.1.2
Additional fire-extinguishing
arrangements
footnote
5.1.2.1 There shall be in each boiler
room or at an entrance outside of the boiler room at least one portable
foam applicator unit complying with the provisions of the Fire Safety
Systems Code.
5.1.2.2 There shall be at least two portable foam
extinguishers or equivalent in each firing space in each boiler room and in each
space in which a part of the oil fuel installation is situated. There shall be not
less than one approved foam-type extinguisher of at least 135 lcapacity or
equivalent in each boiler room. These extinguishers shall be provided with hoses on
reels suitable for reaching any part of the boiler room. In the case of domestic
boilers of less than 175 kW, or boilers protected by fixed water-based local
application fire-extinguishing systems as required by paragraph 5.6, an approved
foam-type extinguisher of at least 135 l capacity is not required.
5.1.2.3 In each firing space there shall
be a receptacle containing at least 0.1 m3 sand, sawdust
impregnated with soda, or other approved dry material, along with
a suitable shovel for spreading the material. An approved portable
extinguisher may be substituted as an alternative.
5.2
Machinery spaces of category A containing internal combustion machinery
5.2.1
Fixed fire-extinguishing
systems
Machinery spaces of category A containing internal
combustion machinery shall be provided with one of the fixed fire-extinguishing
systems in paragraph 4.1.
5.2.2
Additional fire-extinguishing
arrangements
footnote
5.2.2.1 There shall be at least one
portable foam applicator unit complying with the provisions of the
Fire Safety Systems Code.
5.2.2.2 There shall be in each such
space approved foam-type fire extinguishers, each of at least 45 l capacity or equivalent, sufficient in number to enable foam
or its equivalent to be directed onto any part of the fuel and lubricating
oil pressure systems, gearing and other fire hazards. In addition,
there shall be provided a sufficient number of portable foam extinguishers
or equivalent which shall be so located that no point in the space
is more than 10 m walking distance from an extinguisher and that there
are at least two such extinguishers in each such space. For smaller
spaces of cargo ships the Administration may consider relaxing this
requirement.
5.3
Machinery spaces containing
steam turbines or enclosed steam engines
5.3.1
Fixed fire-extinguishing
systems
In spaces containing steam turbines or enclosed
steam engines used for main propulsion or other purposes having in
the aggregate a total output of not less than 375 kW, one of the fire-extinguishing
systems specified in paragraph 4.1 shall
be provided if such spaces are periodically unattended.
5.3.2
Additional fire-extinguishing
arrangements
5.3.2.1 There shall be approved foam
fire extinguishers each of at least 45 l capacity
or equivalent, sufficient in number to enable foam or its equivalent
to be directed on to any part of the pressure lubrication system,
on to any part of the casings enclosing pressure lubricated parts
of the turbines, engines or associated gearing, and any other fire
hazards. However, such extinguishers shall not be required if protection,
at least equivalent to that required by this subparagraph, is provided
in such spaces by a fixed fire-extinguishing system fitted in compliance
with paragraph 4.1.
5.3.2.2 There shall be a sufficient
number of portable foam extinguishersfootnote or
equivalent which shall be so located that no point in the space is
more than 10 m walking distance from an extinguisher and that there
are at least two such extinguishers in each such space, except that
such extinguishers shall not be required in addition to any provided
in compliance with paragraph 5.1.2.2.
5.4
Other machinery spaces
Where, in the opinion of the Administration, a
fire hazard exists in any machinery space for which no specific provisions
for fire-extinguishing appliances are prescribed in paragraphs 5.1, 5.2 and 5.3, there shall be provided in,
or adjacent to, that space such a number of approved portable fire
extinguishers or other means of fire extinction as the Administration
may deem sufficient.
5.5
Additional requirements for passenger
ships
In passenger ships carrying more than 36 passengers,
each machinery space of category A shall be provided with at least
two suitable water fog applicators. footnote
5.6
Fixed local application fire-extinguishing
systems
5.6.1
Paragraph
5.6 shall apply to passenger ships of 500 gross tonnage and
above and cargo ships of 2000 gross tonnage and above.
5.6.2 Machinery spaces of category A
above 500 m3 in volume shall, in addition to the fixed
fire-extinguishing system required in paragraph
5.1.1, be protected by an approved type of fixed water-based
or equivalent local application fire-fighting system, based on the
guidelines developed by the Organization.footnote In
the case of periodically unattended machinery spaces, the fire fighting
system shall have both automatic and manual release capabilities.
In the case of continuously manned machinery spaces, the fire-fighting
system is only required to have a manual release capability.
5.6.3 Fixed local application fire-extinguishing
systems are to protect areas such as the following without the necessity
of engine shutdown, personnel evacuation, or sealing of the spaces:
-
.1 the fire hazard portions of internal combustion
machinery or, for ships constructed before 1 July 2014, the fire hazard
portions of internal combustion machinery used for the ship's main
propulsion and power generation;
-
.2 boiler fronts;
-
.3 the fire hazard portions of incinerators; and
-
.4 purifiers for heated fuel oil.
5.6.4 Activation of any local application
system shall give a visual and distinct audible alarm in the protected
space and at continuously manned stations. The alarm shall indicate
the specific system activated. The system alarm requirements described
within this paragraph are in addition to, and not a substitute for,
the detection and fire alarm system required elsewhere in this chapter.
6 Fire-extinguishing
arrangements in control stations, accommodation and service spaces
6.1
Sprinkler and water spray systems in
passenger ships
6.1.1 Passenger ships carrying more than 36 passengers
shall be equipped with an automatic sprinkler, fire detection and
fire alarm system of an approved type complying with the requirements
of the Fire Safety Systems Code in all control stations, accommodation
and service spaces, including corridors and stairways. Alternatively,
control stations, where water may cause damage to essential equipment,
may be fitted with an approved fixed fire-extinguishing system of
another type. Spaces having little or no fire risk such as voids,
public toilets, carbon dioxide rooms and similar spaces need not be
fitted with an automatic sprinkler system.
6.1.2 In passenger ships carrying not more than
36 passengers, when a fixed smoke detection and fire alarm system
complying with the provisions of the Fire Safety Systems Code is provided
only in corridors, stairways and escape routes within accommodation
spaces, an automatic sprinkler system shall be installed in accordance
with regulation 7.5.3.2.
6.1.3 A fixed pressure water-spraying fire-extinguishing
system complying with the provisions of the Fire Safety
Systems Code shall be installed on cabin balconies of ships
to which regulation 5.3.4 applies, where furniture and furnishings
on such balconies are not as defined in regulations 3.40.1, 3.40.2,
3.40.3, 3.40.6 and 3.40.7.
6.2
Sprinkler systems for cargo ships
In cargo ships in which method IIC specified in regulation 9.2.3.1.1.2 is adopted,
an automatic sprinkler, fire detection and fire alarm system shall
be fitted in accordance with the requirements in regulation 7.5.5.2.
6.3
Spaces containing flammable liquid
6.3.1 Paint lockers shall be protected by:
-
.1 a carbon dioxide system, designed to give a
minimum volume of free gas equal to 40% of the gross volume of the
protected space;
-
.2 a dry powder system, designed for at least
0.5 kg powder/m 3;
-
.3 a water spraying or sprinkler system, designed
for 5 l /m2min. Water spraying systems
may be connected to the fire main of the ship; or
-
.4 a system providing equivalent protection, as
determined by the Administration.
In any case, the system shall be operable from outside the protected
space.
6.3.2 Flammable liquid lockers shall be protected
by an appropriate fire-extinguishing arrangement approved by the Administration.
6.3.3 For lockers of a deck area of less than
4 m2, which do not give access to accommodation spaces,
a carbon dioxide portable fire extinguisher sized to provide a minimum
volume of free gas equal to 40% of the gross volume of the space may
be accepted in lieu of a fixed system. A discharge port shall be arranged
in the locker to allow the discharge of the extinguisher without having
to enter into the protected space. The required portable fire extinguisher
shall be stowed adjacent to the port. Alternatively, a port or hose
connection may be provided to facilitate the use of fire main water.
6.4
Deep-fat cooking equipment
Deep-fat cooking equipment installed in enclosed spaces
or on open decks shall be fitted with the following:
-
.1 an automatic or manual fire-extinguishing system
tested to an international standard acceptable to the Organization;footnote
-
.2 a primary and backup thermostat with an alarm
to alert the operator in the event of failure of either thermostat;
-
.3 arrangements for automatically shutting off
the electrical power upon activation of the fire-extinguishing system;
-
.4 an alarm for indicating operation of the fire-extinguishing
system in the galley where the equipment is installed; and
-
.5 controls for manual operation of the fire-extinguishing
system which are clearly labelled for ready use by the crew.
7 Fire-extinguishing
arrangements in cargo spaces
7.1
Fixed gas fire-extinguishing systems
for general cargo
7.1.1 Except as provided for in paragraph 7.2,
the cargo spaces of passenger ships of 1,000 gross tonnage and upwards
shall be protected by a fixed carbon dioxide or inert gas fire-extinguishing
system complying with the provisions of the Fire Safety Systems Code
or by a fixed high-expansion foam fire-extinguishing system which
gives equivalent protection.
7.1.2 Where it is shown to the satisfaction of
the Administration that a passenger ship is engaged on voyages of
such short duration that it would be unreasonable to apply the requirements
of paragraph 7.1.1 and also in ships of less than 1,000 gross tonnage,
the arrangements in cargo spaces shall be to the satisfaction of the
Administration, provided that the ship is fitted with steel hatch
covers and effective means of closing all ventilators and other openings
leading to the cargo spaces.
7.1.3 Except for ro-ro and vehicle spaces, cargo
spaces on cargo ships of 2,000 gross tonnage and upwards shall be
protected by a fixed carbon dioxide or inert gas fire-extinguishing
system complying with the provisions of the Fire Safety Systems Code,
or by a fire-extinguishing system which gives equivalent protection.
7.1.4 The Administration may exempt from the requirements
of paragraphs 7.1.3 and 7.2, cargo spaces of any cargo ship if constructed,
and solely intended for, the carriage of ore, coal, grain, unseasoned
timber, non-combustible cargoes or cargoes which, in the opinion of
the Administration, constitute a low fire risk.footnote Such exemptions may be granted only if the ship
is fitted with steel hatch covers and effective means of closing ventilators
and other openings leading to the cargo spaces. When such exemptions
are granted, the Administration shall issue an Exemption Certificate,
irrespective of the date of construction of the ship concerned, in
accordance with regulation I/12(a)(vii),
and shall ensure that the list of cargoes the ship is permitted to
carry is attached to the Exemption Certificate.
7.2
Fixed gas fire-extinguishing systems
for dangerous goods
A ship engaged in the carriage of dangerous goods in any
cargo spaces shall be provided with a fixed carbon dioxide or inert
gas fire-extinguishing system complying with the provisions of the
Fire Safety Systems Code or with a fire-extinguishing system which,
in the opinion of the Administration, gives equivalent protection
for the cargoes carried.
7.3
Firefighting for ships constructed on or after 1 January 2016 designed to carry
containers on or above the weather deck
7.3.1 Ships shall carry, in addition to the equipment
and arrangements required by paragraphs 1 and 2, at least one water mist lance.
7.3.1.1 The water mist lance shall consist of a tube
with a piercing nozzle which is capable of penetrating a container wall and producing
water mist inside a confined space (container, etc.) when connected to the fire
main.
7.3.2 Ships designed to carry five or more tiers of
containers on or above the weather deck shall carry, in addition to the requirements
of paragraph 7.3.1, mobile water monitorsfootnote as follows:
7.3.2.1 The mobile water monitors, all necessary hoses,
fittings and required fixing hardware shall be kept ready for use in a location
outside the cargo space area not likely to be cut-off in the event of a fire in the
cargo spaces.
7.3.2.2 A sufficient number of fire hydrants shall be
provided such that:
-
.1 all provided mobile water monitors can be
operated simultaneously for creating effective water barriers forward and aft
of each container bay;
-
.2 the two jets of water required by paragraph
2.1.5.1 can be supplied at the pressure required by paragraph 2.1.6; and
-
.3 each of the required mobile water monitors can
be supplied by separate hydrants at the pressure necessary to reach the top
tier of containers on deck.
7.3.2.3 The mobile water monitors may be supplied by the
fire main, provided the capacity of fire pumps and fire main diameter are adequate to
simultaneously operate the mobile water monitors and two jets of water from fire
hoses at the required pressure values. If carrying dangerous goods, the capacity of
fire pumps and fire main diameter shall also comply with regulation 19.3.1.5, as far
as applicable to on-deck cargo areas.
7.3.2.4 The operational performance of each mobile water
monitor shall be tested during initial survey on board the ship to the satisfaction
of the Administration. The test shall verify that:
-
.1 the mobile water monitor can be securely fixed
to the ship structure ensuring safe and effective operation; and
-
.2 the mobile water monitor jet reaches the top
tier of containers with all required monitors and water jets from fire hoses
operated simultaneously.
8 Cargo tank protection
8.1
Fixed deck foam fire-extinguishing systems
8.1.1 For tankers of 20,000 tonnes deadweight
and upwards, a fixed deck foam fire-extinguishing system shall be
provided in accordance with the requirements of the Fire Safety Systems
Code, except that, in lieu of the above, the Administration, after
having given consideration to the ship's arrangement and equipment,
may accept other fixed installations if they afford protection equivalent
to the above, in accordance with regulation
I/5. The requirements for alternative fixed installations shall
comply with the requirements in paragraph 8.1.2.
8.1.2 In accordance with paragraph 8.1.1, where
the Administration accepts an equivalent fixed installation in lieu
of the fixed deck foam fire-extinguishing system, the installation
shall:
8.1.3 Tankers of less than 20,000 tonnes deadweight
shall be provided with a deck foam fire-extinguishing system complying
with the requirements of the Fire Safety Systems Code.
9 Protection of cargo
pump rooms in tankers
9.1
Fixed fire-extinguishing systems
Each cargo pump-room shall be provided with one of the following
fixed fire-extinguishing systems operated from a readily accessible
position outside the pump-room. Cargo pump-rooms shall be provided
with a system suitable for machinery spaces of category A.
9.1.1 A carbon dioxide fire-extinguishing system
complying with the provisions of the Fire Safety Systems Code and
with the following:
-
.1 the alarms giving audible warning of the release
of fire-extinguishing medium shall be safe for use in a flammable
cargo vapour/air mixture; and
-
.2 a notice shall be exhibited at the controls
stating that due to the electrostatic ignition hazard, the system
is to be used only for fire extinguishing and not for inerting purposes.
9.1.2 A high-expansion foam fire-extinguishing
system complying with the provisions of the Fire Safety Systems Code,
provided that the foam concentrate supply is suitable for extinguishing
fires involving the cargoes carried.
9.1.3 A fixed pressure water-spraying fire-extinguishing
system complying with the provisions of the Fire Safety
Systems Code.
9.2
Quantity of fire-extinguishing medium
Where the extinguishing medium used in the cargo pump-room
system is also used in systems serving other spaces, the quantity
of medium provided or its delivery rate need not be more than the
maximum required for the largest compartment.
10 Fire-fighter's outfits
10.1
Types of firefighter's outfits
10.2
Numbers of fire-fighter's outfits
10.2.1 Ships shall carry at least two
fire-fighter's outfits.
10.2.2 In addition, in passenger ships
there shall be provided:
-
.1 for every 80 m, or part thereof, of the aggregate
of the lengths of all passenger spaces and service spaces on the deck
which carries such spaces or, if there is more than one such deck,
on the deck which has the largest aggregate of such lengths, two fire-fighter's
outfits and, in addition, two sets of personal equipment, each set
comprising the items stipulated in the Fire Safety Systems Code. In
passenger ships carrying more than 36 passengers, two additional fire-fighter's
outfits shall be provided for each main vertical zone. However, for
stairway enclosures which constitute individual main vertical zones
and for the main vertical zones in the fore or aft end of a ship which
do not contain spaces of categories (6), (7), (8) or (12) defined
in regulation 9.2.2.3,
no additional fire-fighter's outfits are required; and
-
.2 on ships carrying more than 36 passengers,
for each pair of breathing apparatus there shall be provided one water
fog applicator which shall be stored adjacent to such apparatus.
10.2.3 In addition, in tankers, two fire-fighter's
outfits shall be provided.
10.2.4 The Administration may require
additional sets of personal equipment and breathing apparatus, having
due regard to the size and type of the ship.
10.2.5 Two spare charges shall be provided
for each required breathing apparatus. Passenger ships carrying not
more than 36 passengers and cargo ships that are equipped with suitably
located means for fully recharging the air cylinders free from contamination,
need carry only one spare charge for each required apparatus. In passenger
ships carrying more than 36 passengers, at least two spare charges
for each breathing apparatus shall be provided
10.2.6 Passenger ships carrying more
than 36 passengers constructed on or after 1 July 2010 shall be fitted
with a suitably located means for fully recharging breathing air cylinders,
free from contamination. The means for recharging shall be either:
-
.1 breathing air compressors supplied from the
main and emergency switchboard, or independently driven, with a minimum
capacity of 60 l/min per required breathing apparatus,
not to exceed 420 l/min; or
-
.2 self-contained high-pressure storage systems
of suitable pressure to recharge the breathing apparatus used on board,
with a capacity of at least 1,200 l per required breathing
apparatus, not to exceed 50,000 l of free air.”
10.3
Storage of fire-fighter's
outfits
10.3.1 The fire-fighter's outfits or
sets of personal equipment shall be kept ready for use in an easily
accessible location that is permanently and clearly marked and, where
more than one fire-fighter's outfit or more than one set of personal
equipment is carried, they shall be stored in widely separated positions.
10.3.2 In passenger ships, at least
two fire-fighter's outfits and, in addition, one set of personal equipment
shall be available at any one position. At least two fire-fighter's
outfits shall be stored in each main vertical zone.
10.4
Fire-fighter's communication
For ships constructed on or after 1 July 2014, a minimum
of two two-way portable radiotelephone apparatus for each fire party
for fire-fighter's communication shall be carried on board. Those
two-way portable radiotelephone apparatus shall be of an explosion-proof
type or intrinsically safe. Ships constructed before 1 July 2014 shall
comply with the requirements of this paragraph not later than the
first survey after 1 July 2018."
|