Appendix - Fire Test Procedures for Fire-Resisting Divisions
of High-Speed Craft
1 General
1.1 Under the provisions of the 1994
HSC Code or 2000 HSC Code, constructions
for use in high-speed craft shall have fire-resisting properties to
the satisfaction of, and be approved by, the Administration. In this
context "fire-resisting property" is the ability of the construction
to insulate/protect an area from the influence of a fire in an adjoining
area by having separating performance during a fire. Such constructions
are fire-resisting bulkheads, decks, ceilings, linings and doors.
1.1.1 Fire-resisting divisions for moderate fire
hazard are classified as "fire-resisting divisions 30".
1.1.2 Fire-resisting divisions for major fire
hazard are classified as "fire-resisting divisions 60".
1.2 The classification shall be expressed in the
form of, for example, "Load bearing fire-resisting deck 60" and "Non-load
bearing fire-resisting bulkhead 30", i.e. including the qualification
on orientation of the division together with a statement if the division
in question is evaluated as load bearing or as non-load bearing.
1.3 Testing of fire-resisting divisions and reporting
shall generally be in accordance with the requirements given in part 3 of this annex. Where additional
interpretation, adaptations and/or supplementary requirements may
be necessary, these are detailed in this part.
1.4 The test shall continue for a minimum of 30
min for fire-resisting divisions 30, or 60 min for fire-resisting
divisions 60, or for an intermediate fire protection time when allowed
in accordance with the 2000 HSC Code.
1.5 The following performance criteria for insulation
and integrity shall be fulfilled within the classification period
(see paragraph 1.4 above):
1.6 In this appendix, testing of fire-resisting
divisions is described in three separate parts, as follows:
-
.1 non-load bearing fire-resisting divisions;
-
.2 load bearing fire-resisting divisions having
a structural metal core as presupposed in part
3 of this annex for "A" class divisions; and
-
.3 other load bearing fire-resisting divisions.
2 Non-Load Bearing Fire-Resisting Divisions
The approach adopted for testing of fire-resisting divisions
which are non-load bearing shall follow the requirements for testing
"B" class divisions in part 3 of
this annex where relevant and appropriate.
3 Load Bearing Fire-Resisting Divisions Having
a Structural Metal Core as Presupposed in Part 3 of this Annex for
“A” Class Divisions
3.1 The approach adopted for testing of load-bearing
fire-resisting divisions having a structural metal core (steel or
aluminium) shall follow the requirements for testing "A" class divisions
in part 3 of this annex, where
relevant and appropriate.
3.2 If the structural core is of aluminium, the
average temperature of the structural core shall not rise more than
200°C above its initial temperature at any time within the classification
period (see paragraph 1.4 above).
4 Load Bearing Fire-Resisting Divisions
4.1 The approach adopted for testing of other
load bearing fire-resisting divisions shall follow the requirements
for testing "B" class divisions in part
3 of this annex where relevant and appropriate.
4.2 In addition, such load bearing divisions shall
be tested with the prescribed static load and they shall maintain
their load bearing ability within the classification period (see paragraph
1.4 above).
4.3 Nature of test specimen
4.3.1 The construction, erection and stiffening
of the test specimen shall be typical of the use in practice.
4.3.2 For vertical divisions (bulkheads), the
minimum overall dimensions for the exposed part of the test specimen
are 2,440 mm width and 2,500 mm height, or full height if the height
is smaller than 2,500 mm.
4.3.3 For horizontal divisions (decks), the minimum
overall dimensions for the exposed part of the test specimen are 2,440
mm width and 3,040 mm length (span), or full length if the length
is smaller than 3,040 mm.
4.4 Mounting of test specimen
4.4.1 A vertical test specimen shall be simply
supported at the top and the bottom and shall not be supported along
its vertical edges.
4.4.2 A horizontal test specimen shall be simply
supported at the two ends and shall not be supported along its edges
parallel to the span.
4.5 Static load
4.5.1 The following levels of loading shall be
applied uniformly, as far as practicable, along the top edge of the
vertical specimen or surface of the horizontal specimen:
The load may be applied hydraulically, mechanically or by
the use of weights.
4.5.2 The loading equipment shall be able to simulate
the conditions of loading, as appropriate, for the test construction.
The loading equipment shall also be capable of maintaining the test
load at a constant value (to within ± 5% of the required value)
without changing its distribution for the duration of the load-bearing
capacity period; it shall not significantly influence the heat transfer
through the specimen nor impede the use of the thermocouple insulating
pads; it shall not interfere with the measurement of surface temperature
and/or deformation and shall permit general observation of the unexposed
face.
4.5.3 For decks, the total area of the contact
points between the loading equipment and the test specimen surface
shall not exceed 10% of the total area of the surface of a horizontal
test specimen. The equipment shall be capable of following the maximum
deformation and the rate of deformation of the test specimen. For
bulkheads, the loading equipment has to produce a load uniformly applied
to the total width of the bulkhead.
4.5.4 If the tested assembly includes load bearing
elements such as beams, they shall be exposed to the furnace on all
faces except for the face in contact with the specimen and shall not
be placed at less than 200 mm from the furnace walls.
4.5.5 In practice, it may be difficult to produce
a uniform load, especially on decks. When determining a load distribution
that is representative of the standard conditions described in paragraphs
4.4.2 and 4.5.1, the laboratory shall consider the degrees of freedom,
maximum shear force and bending moment.
4.5.6 Mounting methods and loading conditions
different to those in paragraphs 4.4.2 and 4.5.1 may be used. In that
case, the test conditions and load distribution shall be acceptable
to the Administration.
4.5.7 The test report shall include justifications
of approximations to uniform load and mounting. The report shall include
a description of load repartition in terms of force, surface of contact
and position of these contacts.
4.5.8 The test load shall be applied at least
15 min before the commencement of the heating period.
4.6 Deformation
4.6.1 Deformation measurements shall be made using
equipment employing mechanical, optical or electrical techniques.
Instrumentation for the measurement of deflection of the test specimen
shall be located so as to provide data in terms of the amount and
rate of deflection during the fire test.
4.6.2 The deformation data shall be recorded to
an accuracy of ± 2 mm during the testing period.
4.6.3 For a bulkhead, measurement shall be made
of the axial contraction and of the horizontal deflection.
4.6.4 For a deck, measurement shall be made of
the vertical deflection.
4.7 Performance criteria for load bearing ability
The test specimen shall be deemed to have failed if it is
no longer able to support the test load. Support of the test load
is determined by both the amount and the rate of deflection. Since
relatively rapid deflections can occur until stable conditions are
reached, the rate of deflection criteria of decks is not applied until
a deflection of L/30 has been exceeded. For the purposes of this part,
the following criteria apply:
-
.1 bulkheads:
-
.1 limiting axial contraction of h/100 mm; and
-
.2 limiting rate of axial contraction of 3 h/1,000
mm/min,
-
where:
-
.2 decks:
-
.1 limiting deflecting of (L)2/400
d mm; and
-
.2 limiting rate of deflection of (L)2/9,000
d mm/min,
-
where:
5 Test Report
The test report shall include the following information
as a minimum. A clear distinction shall be made between the data provided
by the sponsor and the data determined by the test:
-
.1 reference that the test was carried out in
accordance with part 11 of the 2010 FTP Code (see also subparagraph
.2 below);
-
.2 any deviations from the test method;
-
.3 name and address of the testing laboratory;
-
.4 date and identification number of the report;
-
.5 name and address of the sponsor;
-
.6 name and/or identification of the product tested;
-
.7 the name of the manufacturer of the test specimen
and of the products and components used in the construction;
-
.8 type of the product, e.g. bulkhead, ceiling,
door, window, duct penetration, etc.;
-
.9 classification of test per paragraph 1.6;
-
.10 the constructional details of the test specimen,
including description and drawing and principal details of components.
All the details requested in paragraph 2 shall be given. The description
and the drawings which are included in the test report shall, as far
as practicable, be based on information derived from a survey of the
test specimen. When full and detailed drawings are not included in
the report, then the applicant's drawing(s) of the test specimen shall
be authenticated by the laboratory and at least one copy of the authenticated
drawing(s) shall be retained by the laboratory; in this case reference
to the applicant's drawing(s) shall be given in the report together
with a statement indicating the method of endorsing the drawings;
-
.11 all properties of materials used that have
a bearing on the fire performance of the test specimen together with
measurements of thickness, density and, where applicable, the moisture
and/or organic content of the insulation material(s) as determined
by the test laboratory;
-
.12 method of applying load and quantity of the
load, if applicable;
-
.13 date of the test specimen arrival;
-
.14 details of specimen conditioning;
-
.15 date of test;
-
.16 test results:
-
.1 information concerning the location of all
thermocouples fixed to the specimen, together with tabulated data
obtained from each thermocouple during the test. Additionally, a graphical
depiction of the data obtained may be included. A drawing shall be
included which clearly illustrates the positions of the various thermocouples
and identifies them relative to the temperature-time data;
-
.2 the average and the maximum temperature rises
and the average core temperature rise, when applicable, recorded at
the end of the period of time appropriate to the insulation performance
criteria for the relevant classification or, if the test is terminated
due to the insulation criteria having been exceeded, the times at
which limiting temperatures were exceeded; and
-
.3 the maximum deflection of the specimen. In
case of doors, the maximum deflection at the centre of the door specimen
and the maximum displacement of each corner of the door leaf relative
to the door frame;
-
.17 the classification attained by the test specimen
shall be expressed in the form of "load-bearing fire-resisting divisions
60 bulkhead", i.e. including the qualification on orientation of the
division. The result shall be presented in the test report in the
following manner under the heading "Classification": "A bulkhead constructed
as described in this report may be regarded as an "load-bearing fire-resisting
divisions 60" class bulkhead according to part 11 of annex 1 to the
2010 FTP Code.";
-
.18 the name of the representative of the Administration
present at the test. If the Administration requires prior notification
of test and a representative does not witness the test, a note to
this effect shall be made in the report in the following form:
-
"The … (name of the Administration) … was notified
of the intention to conduct the test detailed in this report and did
not consider it necessary to send a representative to witness it.";
and
-
.19 the statement:
-
"The test results relate to the behaviour of the test specimens
of a product under the particular conditions of the test; they are
not intended to be the sole criterion for assessing the potential
fire hazard of the product in use.".
|