Paragraph 11.3.6 – Fire protection and extinction, Water-spray system
Where "F.O. tanks" are installed at the after end of the aftermost hold space or at the
forward end of the forwardmost hold space instead of cofferdams as allowed for in
paragraphs 3.1.2 and 3.1.3 of the IGC Code, the weather deck area above these tanks
should be regarded as a "cargo area" for the purpose of applying paragraph 11.3.6.
Paragraph 11.4.8 – Fire protection and extinction, Dry chemical powder
fire-extinguishing systems
Testing arrangements should involve the discharge using dry chemical powder from all
monitors and hand hose lines on board but it is not required that there is a full
discharge of the installed quantity of dry powder. This testing can also be used to
satisfy the requirement that the piping is free of obstructions, in lieu of blowing
through with dry air all the distribution piping. However, after the completion of this
testing, the system, including all monitors and hand hose lines, should be blown through
with dry air but only for the purpose of the system subsequently being clear from any
residues of dry chemical powder.