Appendix 1 – Fire Test Procedures for Surface Flammability
of Bulkhead, Ceiling, Deck Finish Materials and Primary Deck Covering
Warning
The use of this test method involves the generation of very
high-heat flux levels which are capable of causing ignition of some
materials such as clothing following even brief exposures. Precautions
shall be taken to avoid accidental ignitions of this type.
The attention of the user of this test is drawn to the fact
that the fumes from burning materials often include carbon monoxide.
Other more toxic products may in many instances be produced. Suitable
precautions shall be taken to avoid any extended exposure to these
fumes.
1 Scope
This appendix specifies a procedure for measuring fire characteristics
of bulkhead, ceiling, deck finish materials and primary deck coverings
as a basis for characterizing their flammability and thus their suitability
for use in marine construction.
2 Normative References
The following normative documents contain provisions which
constitute provisions of this appendix:
-
.1 ISO 13943, Fire safety – Vocabulary;
and
-
.2 ISO 5658-2, Reaction to fire tests –
Spread of Flame – Part 2: Lateral spread on building and transport
products in vertical configuration.
3 Definitions
For the purposes of this appendix 1, the terms and definitions
given in standards ISO 13943 and ISO 5658-2 and the following apply.
3.1
Backing board is a non-combustible
board with the same width and length as the test specimen and 12.5
± 3 mm thick and having the density of 950 ± 100 kg/m3, used to back the specimen.
3.2
Calibration board is a dummy
specimen as defined by figure 11 of appendix 2, intended only for
use in calibration of heat flux gradient along with specimen.
3.3
Compensating thermocouple is
a thermocouple for the purpose of generating an electrical signal
representing long-term changes in stack metal temperatures. A fraction
of the signal generated is subtracted from the signal developed by
the stack gas thermocouples.
3.4
Critical flux at extinguishment is
an incident heat flux level at the surface of a specimen at the point
along its horizontal centreline where the flame ceases to advance
and may subsequently go out.
3.5
Dummy specimen is a specimen
used for standardizing the operating condition of the equipment. It
shall be a non-combustible board (for example, calcium silicate board)
of oven-dry density of 950 ± 100 kg/m3 and shall
measure from 795 mm to 800 mm long, from 150 mm to 155 mm wide and
25 ± 2 mm thick.
3.6
Fume stack is a box-like duct
with thermocouples and baffles through which flames and hot fumes
from a burning specimen pass. Its purpose is to permit measurement
of the heat release from the burning specimen.
3.7
Heat for ignition is the product
of the time from initial specimen exposure until the flame front reaches
the 150 mm position and the flux level at this position; this latter
obtained in prior calibration of the apparatus.
3.8
Heat release of specimen is the
observed heat release under the variable flux field imposed on the
specimen and measured as defined by the test method.
3.9
Heat for sustained burning is
the product of time from the start of exposure of a specimen to the
arrival of the flame front at a specified position and the incident
flux corresponding to that position measured on a non-combustible
calibration board. This shall be calculated for each station starting
at the 150 mm station, but it shall not be calculated for a given
station unless the flame propagates more than halfway to the next
station as viewed along the centreline of the specimen.
3.10
Reverberatory wires is a wire
mesh located in front of, but close to, the radiating surface of the
panel heat source. This serves to enhance the combustion efficiency
and increase the radiance of the panel.
3.11
Viewing rakes is a set of bars
with wires spaced at 50 mm intervals for the purpose of increasing
the precision of timing flame front progress along the specimen.
4 Principle of the Test
4.1 This test provides methods for evaluating
flammability characteristics of 155 mm x 800 mm specimens in vertical
orientation.
4.2 The specimens are exposed to a graded radiant
flux field supplied by a gas-fired radiant panel. Means are provided
for observing the times to ignition, spread and extinguishment of
flame along the length of the specimen as well as for measuring the
compensated millivolt signal of the stack gas thermocouples as the
burning progresses. Experimental results are reported in terms of:
heat for ignition, heat for sustained burning, critical flux at extinguishment
and heat release of specimen during burning.
5 Facility and Apparatus Requirements
5.1 General
The test apparatus, except the equipment for measurement
of heat release (i.e. fume stack and thermocouples for it), is specified
in standard ISO 5658-2. A detailed description of the facility and
apparatus required for conduct of this test is included in appendix
2 to this part. Compliance with the appendix forms an essential requirement
of the test method. The equipment needed may be summarized as follows.
5.1.1 Special test room fitted with fume exhaust
system as well as fresh air inlet.
5.1.2 Radiant panel frame fitted with blower or
other source of combustion air, a methanefootnote or
natural gas supply system with suitable safety controls, and a radiant
panel heat source, with reverberatory wires, arranged to radiate on
a vertical specimen. Alternatively, an electrically-heated radiant
source of the same dimensions may be used provided it can expose the
specimen to the heat flux distribution shown in table 1 of appendix
2. The effective source temperature of any radiant panel is not greater
than 1,000°C.
5.1.3 The specimen holder frame, three specimen
holders, a pilot burner, specimen holder guides, viewing rakes and
a viewing mirror.
5.1.4 A specimen fume stack with both stack gas
and stack temperature compensating thermocouples together with a means
for adjusting the magnitude of the compensation signal.
5.1.5 Instrumentation comprising a chronograph,
digital or sweep second electric clock, a digital millivoltmeter,
a two-channel millivolt recorder, gas-flowmeter, heat flux meters,
a wide angle total radiation pyrometer and a stopwatch. Use of a data
acquisition system to record both panel radiance and the heat release
stack signal during test will facilitate data reduction.
6 Calibration
Mechanical, electrical and thermal calibrations shall be
performed as described in appendix 2. These adjustments and calibrations
shall be performed following initial installation of the apparatus
and at other times as the need arises.
6.1 Monthly verification
The calibration of the flux distribution on the specimen
and the proper operation of the fume stack with its thermocouple system
shall be confirmed by monthly tests, or at more frequent intervals
if this is found necessary (see paragraphs 4.3 and 4.6 of appendix
2).
6.2 Daily verification
As a means of assuring continued proper adjustment of the
apparatus, the following tests shall be performed on a daily basis
or more frequently if the nature of the specimens makes this necessary.
6.2.1
Adjustment of the pilot burner
6.2.1.1 Adjust the propane gas and air flow rates
to about 0.4 l/min and 1 l/min, respectively,
to provide a flame length of 230 ± 20 mm in the vertical orientation.
When viewed in a darkened room, the flame shall extend about 40 mm
above the vertical specimen holder (see figure 6 of appendix 2). Record
the flow rates of propane and air to the pilot burner.
6.2.1.2 Adjust the impingement zone of the flame
onto the dummy specimen by moving the burner tube towards or away
from the plane of the exposed surface of the dummy specimen. Rotate
the pilot burner tube in its holder until the flame impinges over
the top half of the exposed specimen height.
6.2.1.3 The pilot flame shall be checked and,
if necessary, adjusted in the way stated above every day. The nature
of some specimens may make this necessary to be done more frequently.
6.2.2
Stack gas thermocouples
The stack gas thermocouples shall be cleaned by light brushing
at least daily. This cleaning may be required even more frequently,
in some instances before each test, when materials producing heavy
soot clouds are tested. These thermocouples shall also be individually
checked for electrical continuity to ensure the existence of a useful
thermojunction. Following daily cleaning of the parallel connected
stack gas thermocouples, both they and the compensating junction shall
be checked to verify that the resistance between them and the stack
is in excess of 106 ohms.
6.3 Continuous monitoring of operation
6.3.1 A dummy specimen shall remain mounted in
the position normally occupied by a specimen whenever the equipment
is in stand-by operation. This is a necessary condition of the continuous
monitoring procedure which is accomplished by measuring:
-
.1 the millivolt signals from both the stack thermocouples
and the total radiation pyrometer mounted securely on the specimen
holder frame facing the surface of the radiant panel; or
-
.2 the millivolt signals from both the stack thermocouples
and a heat flux meter positioned at 350 mm from the exposed hot end
of a dummy specimen as defined in paragraph 3.5 (see paragraph 4.3.2
of appendix 2).
6.3.2 Either of these measurement methods would
be satisfactory for determining that an appropriate thermal operating
level has been achieved. The use of the radiation pyrometer is preferable
since it permits continuous monitoring of the panel operating level
even when tests are in progress. Both signals shall remain essentially
constant for 3 min prior to the test. The observed operating level
of either the radiation pyrometer or the heat flux meter shall correspond,
within 2%, to the similar required level specified in table 1 of appendix
2 and referred to in the calibration procedure mentioned in paragraph
6.1 above.
7 Specimens
7.1 Number Required
At least six specimens shall be provided for each different
exposed surface.
7.1.2
Required number for the test
Three specimens shall be tested for each different exposed
surface of the product evaluated and applied. Condition of retest
is described in paragraph 8.3.
7.2 Dimensions
7.2.1 The specimens shall measure from 150 mm
to 155 mm wide and from 795 mm to 800 mm long, and shall be representative
of the product.
7.2.2 Specimen thickness: materials and composites
of normal thickness 50 mm or less shall be tested using their full
thickness. For materials and composites of normal thickness greater
than 50 mm, the required specimens shall be obtained by cutting away
the unexposed face to reduce the thickness between 47 mm and 50 mm.
7.3 Substrate
7.3.1
Substrate of surface material
and floor coverings
Materials and composite materials shall be tested using
their full thickness, attaching them, by means of an adhesive if appropriate,
to the substrate to which they will be attached in practice. The test
specimen shall reflect actual application.
7.3.2
Substrate of primary deck covering
The specimens shall be applied to a steel plate having a
thickness of 3 ± 0.3 mm. The specimens shall have a nominal
thickness; the components and construction of the primary deck covering
shall reflect actual application.
7.4 Composite materials
7.4.1 Assembly shall be as specified in paragraph
7.2. However, where thin materials or composites are used in the fabrication
of an assembly, the presence of an air gap and/or the nature of any
underlying construction may significantly affect the flammability
characteristics of the exposed surface. The influence of the underlying
layers shall be recognized and care taken to ensure that the test
result obtained on any assembly is relevant to its use in practice.
7.4.2 Vapour barriers used in conjunction with
insulation shall be tested without any other components that will
shield the barrier being tested from the radiant panel. The substrate
of the specimen shall reflect actual application on ships.
7.5 Metallic facings
If a bright metallic faced specimen is to be tested, it
shall be tested as it is.
7.6 Marking specimens
A line shall be marked centrally down the length of the
face to be tested of each specimen. Caution shall be exercised to
avoid the use of a line which would influence specimen performance.
7.7 Conditioning of specimens
Before test, the specimens shall be conditioned to constant
moisture content, at a temperature of 23 ± 2°C, and a relative
humidity of 50 ± 5%. Constant moisture content is considered
to be reached when, following two successive weighing operations,
carried out at an interval of 24 h, the measured masses do not differ
by more than 0.1% of the mass of the specimen.
8 Test Procedure
8.1 General considerations
The test method involves mounting the conditioned specimen
in a well-defined flux field and measuring the time of ignition, spread
of flame and its final extinguishment, together with a stack thermocouple
signal as an indication of heat release by the specimen during burning.
8.1.1 Prepare a properly-conditioned specimen
for test in a cool holder away from the heat of the radiant panel.
Prior to insertion in the specimen holder, the back and edges of the
specimen shall be wrapped in a single sheet of aluminium foil of 0.02
mm thickness and dimensions of 175 + a mm x 820 + a mm where "a" is
twice the specimen thickness. When inserted in the specimen holder
each specimen shall be backed by a cool backing board. When mounting
non-rigid specimens in the holder, shims shall be placed between the
specimen and holder flange to ensure that the exposed specimen face
remains at the same distance from the pilot flame as a rigid specimen.
For such materials, the shims may often only be required for a 100
mm length at the hot end of the specimen.
8.1.2 The dummy specimen in a specimen holder
shall be mounted in position facing the radiant panel. The equipment
fume exhaust system shall be started.
8.1.3 The radiant panel is operated to realize
the test conditions as specified in paragraph 6.3. Start the millivolt
recorder recording the output signal of the stack thermocouples, as
well as the signal from the total radiation pyrometer or heat flux
meter positioned as described in paragraph 6.3.1.2.
8.1.4 When the radiant panel and stack signals
have attained equilibrium, after the preheat period, light the pilot
flame, adjust its fuel flow rate and observe both signals for at least
3 min and verify continued signal stability.
8.1.5 After both signals reach stable levels,
remove the dummy specimen holder and insert the specimen in the test
position within 10 s. Immediately start both the clock and chronograph.
8.1.6 Operate the event marker of the chronograph
to indicate the time of ignition and arrival of the flame front during
the initial rapid involvement of the specimen. The arrival at a given
position shall be observed as the time at which the flame front at
the longitudinal centreline of the specimen is observed to coincide
with the position of two corresponding wires of the viewing rakes.
These times are recorded manually both from measurement on the chronograph
chart and from observations of the clock. As far as possible, the
arrival of the flame front at each 50 mm position along the specimen
shall be recorded. Record both the time and the position on the specimen
at which the progress of flaming combustion ceases. The panel operating
level, as well as stack signals, shall be recorded throughout the
test and continued until test termination.
8.1.7 Throughout the conduct of the test, no change
shall be made in the fuel supply rate to the radiant panel to compensate
for variations in its operating level.
8.2 Duration of test
8.2.1 The test shall be terminated, the specimen
removed, and the dummy specimen in its holder reinserted when any
one of the following is applicable:
-
.1 the specimen fails to ignite after a 10 min
exposure; or
-
.2 3 min have passed since all flaming from the
specimen ceased or 10 min exposure, whichever is longer.
8.2.2 Operations in paragraphs 8.1.1 to 8.1.7
shall be repeated for two additional specimens (see paragraph 8.3).
8.3 Conditions of retest
8.3.1 In the event of failure, during test of
one or more specimens, to secure complete flame spread times or a
reasonable heat release curve, the data secured shall be rejected
and a new test or tests performed. Such failures might involve, but
not be limited to, incomplete observational data or malfunction of
data logging equipment. Excessive stack signal baseline drift shall
also require further equipment stabilization and retest.
8.3.2 If a specimen shows extensive loss of incompletely
burned material during test, at least one additional specimen, restrained
in the testing frame by poultry netting, shall be tested and the data
secured reported separately.
8.3.3 The following procedures shall be taken
in relation to the behaviour of the specimen during the test:
-
.1 if the pilot flame extinguishes: report occurrence
and reject data and repeat test; or
-
.2 if the specimen breaks up and falls out of
the specimen holder, report the behaviour, but classify on basis of
worst performance with and without specimen restraint in paragraph
8.3.2.
8.4 Observations
In addition to the recording of the experimental data, observations
shall be made and recorded on the behaviour of the specimen including
but not limited to flashing, unstable flame front, sparks, glowing,
charring, melting, flaming drips, disintegration of the specimen,
fissures, fusion, changes in form.
9 Derived Fire Characteristics
Experimental results shall be reported in terms of the thermal
baseline of the output from the thermocouple circuit and measurements
of incident heat flux measured with a dummy specimen in place. The
results shall not be adjusted to compensate for changes in the thermal
output of the radiant panel and the pilot flame during the conduct
of the test. The following data shall be derived from the test results.
9.1 Heat for ignition
As defined in paragraph 3.7.
9.2 Heat for sustained burning
A list of the values of this characteristic as defined in
paragraph 3.9.
9.3 Average heat for sustained burning
9.3.1 An average of the values for the characteristic
defined in paragraph 3.9 measured at different stations, the first
at 150 mm and then at subsequent stations at 50 mm intervals through
the final station or the 400 mm station, whichever value is the lower.
9.3.2 For each specimen where the flame front
does not reach the 175 mm position, the heat of sustained burning
is not defined. If the heat of sustained burning is not defined for
one specimen, Qsb is calculated using the data from the
other two specimens. If the heat of sustained burning is not defined
for two specimens, Qsb is calculated using the data from
the third specimen. If the heat of sustained burning is not defined
for all three specimens, Qsb is undefined and the criterion
of Qsb is deemed to have been met.
9.4 Critical flux at extinguishment
A list of the values of this characteristic for the specimens
tested and the average of these values (see paragraph 3.4).
9.5 Heat release of the specimen
Both a heat release time curve and a listing of the peak
and total integrated heat release shall be secured from the experimental
data. They shall be corrected for the non-linearity of the heat release
calibration curve. The curve of the millivolt signal from the stack
thermocouples shall include at least 30 s of the initial 3 min steady
state verification period as well as the starting transient just prior
to and following specimen insertion. In converting millivolt signals
to heat release rate, the zero release level of the calibration curve
shall be set at the level of the initial steady state just prior to
test of the specimen involved (see figure 10 of appendix 2).
The total heat release is given by integration of the positive
part of the heat release rate during the test period (see figure 10
of appendix 2).
9.5.2
Peak heat release rate
The peak heat release rate is the maximum of the heat release
rate during the test period (see figure 10 of appendix 2).
10 Test Report
The test report shall include the following information
as a minimum. A clear distinction shall be made between the data provided
by the sponsor and data determined by the test:
-
.1 reference that the test was carried out in
accordance with part 5 of the annex to the 2010 FTP Code (also see
subparagraph .2 below);
-
.2 any deviations from the test method;
-
.3 name and address of the testing laboratory;
-
.4 date and identification number of the report;
-
.5 name and address of the sponsor;
-
.6 name and address of the manufacturer/supplier,
if known;
-
.7 type of the material, i.e. surface finish,
floor covering, primary deck covering, pipes, etc.;
-
.8 name and/or identification of the product tested;
-
.9 description of the sampling procedure, where
relevant;
-
.10 description of the product tested including
density and/or mass per unit area, thickness and dimensions, colour,
quantity and number of any coating, together with details of the construction
of the product;
-
.11 description of the specimen including density
and/or mass per unit area, thickness and dimensions, colour, quantity
and number of any coating, orientations tested and face subject to
the test, and construction;
-
.12 date of sample arrival;
-
.13 details of specimen conditioning;
-
.14 date of test;
-
.15 test results:
-
.1 duration of each test;
-
.2 derived fire characteristics as described in
paragraph 9; and
-
.3 observations recorded in accordance with paragraph
8.4; and
-
.16 determination on whether the tested material
meets the performance criteria in paragraphs 3 and 4 of this part.
|