Appendix 2 – Testing of Windows, Fire Dampers,
Pipe and Duct Penetrations and Cable Transits
Introduction
This appendix covers the testing of windows, fire dampers,
pipe penetrations and cable transits, all of which may be incorporated
within "A" class divisions.
Irrespective of the fact that this appendix is written only
for "A" class divisions, the prescriptions given can be used by analogy
when testing windows, fire dampers, pipe and duct penetrations and
cable transits incorporated in "B" class divisions, where appropriate.
The testing and reporting of these components shall be generally
in accordance with the requirements given in appendix 1 to this part.
Where additional interpretation, adaptations and/or supplementary
requirements may be necessary, these are detailed in this appendix.
Since it is not possible to introduce the distortions which
are experienced by the structural core during tests corresponding
to procedures given in this appendix, into specimens of smaller scale,
all the tests of the components covered by this appendix shall be
undertaken with those components installed in full-size dimensioned
structural cores as specified in appendix 1.
A.I – Windows
1 General
1.1 The term window is taken to include windows,
sidescuttles and any other glazed opening provided for light transmission
or vision purposes in "A" class bulkheads. Windows in "A" class doors
are considered to be part of the door and they shall be tested within
the appropriate door.
1.2 The approach adopted for testing windows shall
generally follow the requirements for testing "A" class doors where
relevant and appropriate.
2 Nature of Test Specimens
2.1 Dimensions
2.1.1 The test shall be conducted on the window
of the maximum size (in terms of both the width and the height) for
which approval is sought.
2.1.2 The test shall be conducted on a window
of the maximum size (in terms of both the height and the width) and
the type of the glass pane and/or the minimum thickness of the glass
pane or panes and gaps, if appropriate, for which approval is sought.
Test results obtained on this configuration shall, by analogy, allow
approval of windows of the same type, with lesser dimensions in terms
of height and width and with the same or greater thickness.
2.2 Design
2.2.1 The bulkhead which includes the window shall
be insulated to class "A-60" on the stiffened face, which shall be
the face exposed to the heating conditions of the test. This is considered
to be most typical of the use of windows on board ships. There may
be special applications of windows where the Administration considers
it appropriate to test the window with the insulation of the bulkhead
to the unexposed face of the structural core, such as the window on
front bulkhead of the tanker, or within bulkheads other than class
"A-60".
2.2.2 The window shall be positioned within the
bulkhead, shown in figure 1 of appendix 1, at that height which is
intended for practical application. When this is not known, the window
shall be positioned with the top of its frame as close as possible,
but not closer than 300 mm, to the top of the bulkhead.
3 Instrumentation
When a window is required by the Administration to be of
a classification other than class "A-0", thermocouples shall be fixed
to the window pane as specified for the leaf of a door. In addition,
thermocouples shall be provided to the window frame, one at mid-length
of each perimeter edge. When windows are fitted with transoms and/or
mullions, five thermocouples shall be fixed to each window pane as
specified for the leaf of a door, and, in addition to the thermocouples
fixed to the window frame, a single thermocouple shall be fixed at
mid-length of each transom or mullion member.
4 Method of Test
4.1 Temperature
For the calculation of the average temperature rise on the
unexposed face, only those thermocouples fixed to the face of the
window pane(s) shall be used.
4.2 Cotton-wool pad and gap gauges
For windows which are to be of a classification "A-0", the
cotton-wool pad test need not be used to evaluate the integrity of
a window since radiation through the window pane could be sufficient
to cause ignition of the cotton-wool pad. In such cases cracks or
openings in windows shall not be such as to allow the gap gauges to
enter in the manner described in paragraph 8.4.4 of appendix 1.
5 Hose-Stream Test
5.1 General
This procedure is an optional requirement and may be requested
by some Administrations for windows used in specific areas of a ship.
The window is subjected to the impact, erosion and cooling effects
of a hose stream.
5.2 Method of test
5.2.1 The hose-stream test shall be applied to
the exposed face of the specimen immediately, but at least within
not more than 1.5 min following the termination of the heating period.
5.2.2 The water stream is delivered through a
standard fire hose and discharged through a 19 mm nozzle of tapered
smooth-bore pattern without shoulder at the orifice. The nozzle orifice
shall be 6 m from the centre and normal to the exposed face of the
specimen.
5.2.3 The water pressure at the nozzle shall be
310 kPa when measured with the water flow in progress.
5.2.4 The duration of application of the hose
stream to the surface of the specimen shall be 0.65 min for each square
metre of the exposed area of the specimen. The stream shall be directed
firstly at the centre and then at all parts of the exposed face, changes
in direction being made slowly.
5.3 Performance criteria
5.3.1 For the calculation of the average temperature
rise on the unexposed face, only those thermocouples fixed to the
face of the window pane(s) shall be used.
5.3.2 For the judgment of the maximum temperature
rise on the unexposed face, all the thermocouples fixed to the face
of the window pane(s), window frame, transoms and mullions shall be
used.
5.3.3 The specimen is considered to have satisfied
the criteria of the hose-stream test if no openings develop during
the application of the stream which allow water to pass to the unexposed
face.
5.3.4 The window shall be considered to have failed
the hose-stream test if an opening develops that allows an observable
projection of water from the stream beyond the unexposed surface during
the hose-stream test. Gap gauges need not be applied during or after
the hose stream test.
A.II – Fire Dampers
1 General
1.1 "A" class divisions may have to be pierced
for the passage of ventilation ducting, and arrangements shall be
made to ensure that the effectiveness of the division in relation
to the criterion for integrity, as specified in paragraph 3 of Part
3 , is not impaired. Provisions shall also be made to ensure that,
shall a fire be initiated within, or gain access to, ventilation ductwork,
such a fire does not pass through the division within the ductwork.
1.2 To provide for both these requirements, fire
dampers are provided within or fixed to spigots or coamings which
are welded to the structural core and are insulated to the same standard
as the division.
2 Nature of the Test Specimen
2.1 Dimensions
The maximum sizes (in terms of both the width and the height,
or the diameter) of each type of fire damper for which approval is
sought shall be tested in both vertical and horizontal orientation.
2.2 Design
2.2.1 A bulkhead which includes the damper shall
be constructed in accordance with paragraph 2.1 of appendix 1 and
shall be insulated to class "A-60" on the stiffened face, which shall
be the face which is not exposed to the heating conditions of the
test. A deck which includes the damper shall be constructed in accordance
with paragraph 2.2 of appendix 1 and shall be insulated to class "A-60"
on the stiffened face, which shall be the face which is exposed to
the heating conditions of the test.
2.2.2 Fire dampers shall be incorporated into
or fixed to coamings or a spigot, which shall be welded or bolted
into the structural core.
-
The length on the unexposed side = (450 mm or a needed insulation
length for a damper under test) (Lunexp) + 50 mm.
-
The thickness of the coaming or spigot shall be as follows:
Widthfootnote or diameter of the duct
|
Minimum thickness of coaming
|
Up to and including 300
mm
|
3 mm
|
760 mm and
over
|
5 mm
|
-
For widths or diameters of ducts in excess of 300 mm but
less than 760 mm, the thickness of the coaming or spigot shall be
obtained by interpolation
-
The coaming or spigot shall be insulated as shown in figure
A1.
2.2.3 The coamings or spigots (including insulation)
shall be positioned only in the top half of a bulkhead. Where more
than one damper is included in a bulkhead, the top edges of all dampers
should be, as far as possible, at the same height. These shall be
no closer than 200 mm from the edges of a bulkhead or deck. Where
more than one damper is to be tested simultaneously in a division,
the distance between adjacent coamings or spigots (including insulation)
shall not be less than 200 mm.
2.2.4 The fire dampers shall be positioned on
the exposed face of the bulkhead or deck. The distance between the
fire damper centre and the structural core shall be at least 225 mm.
The operative control of a damper is positioned on the exposed
side of the division. When a damper is mounted in the bulkhead the
fuse element should be situated at the lowest level of the damper
as in practice.
2.2.5 Fire dampers which are operated automatically
shall be in the open position at the start of the test and shall be
closed by an automatic device. The damper shall be in the closed position
within 2 min after the commencement of the test. If the fire damper
fails to close after 2 min from the start of the test, the fire damper
shall be deemed to have failed and the test shall be discontinued.
2.2.6 Fire dampers which are operated with a manual
system shall be closed at the test time of 1 min.
3 Instrumentation
3.1 Positioning of thermocouples on the specimen
3.1.1 For each fire damper, two thermocouples
where the widthfootnote or diameter of a damper
is not more than 200 mm and four thermocouples when that is over 200
mm shall be fixed to the unexposed face at each of the following locations:
-
.1 on the surface of the insulation provided to
the coaming or spigot at a distance of 25 mm from the unexposed surface
of the divisions; and
-
.2 on the surface of the coaming or spigot at
a distance of 25 mm from where the coaming or spigot emerges from
its insulation.
3.1.2 In the damper where the size exceeds 200
mm, four thermocouples, for each of the positions indicated in paragraphs
3.1.1.1 and 3.1.1.2, shall be fixed. One of the thermocouples shall
be fixed at the centre of each side of the coaming or spigot.
3.1.3 In the damper where the size is not more
than 200 mm, two thermocouples, for each of the positions indicated
in paragraphs 3.1.1.1 and 3.1.1.2, shall be fixed. One of the thermocouples
shall be fixed at the centre of opposing sides of the coaming or spigot
and for dampers in bulkheads situated on the top and bottom surface
of the coaming or spigot.
4 Performance Criteria
4.1 It will not always be possible to utilize
the cotton-wool-pad test to evaluate the integrity of a fire damper
since radiation through the damper could be sufficient to cause ignition
of the cotton-wool pad. In such cases, cracks or openings in fire
dampers shall not be such as to allow the gap gauges to enter in the
manner described in paragraph 8.4.4 of appendix 1.
4.2 The performance of fire dampers may be related
to their ability to satisfy both the insulation and the integrity
criteria or may be related only to the requirements for integrity,
depending on the requirements of the Administration.
4.3 If evaluation of insulation is required, the
temperature rise at any point on the surface shall not exceed 180°C
above the initial temperature. The average temperature rise shall
not be used for this purpose.
A.III – Pipe and Duct Penetrations
1 General
1.1 "A" class divisions may have to be provided
with apertures to allow them to be penetrated by service pipes and
ducts, and it is necessary to reinstate the insulation and/or integrity
performance of the division at the position where it has been penetrated.
1.2 Administrations may have different requirements
relating to the need to classify pipe and/or duct penetrations, e.g.,
related to the pipes' diameter and their direct attachment or not
to the structural core.
1.3 This section refers from here on to pipe penetrations
but may be read as equally applicable to duct penetrations.
2 Nature of the Test Specimen
2.1 Dimensions
The maximum and minimum sizes (in terms of both the width
and the height, or diameter) of each type of pipe penetration for
which approval is sought shall be tested in both vertical and horizontal
orientation.
2.2 Design
2.2.1 A bulkhead which includes the pipe penetration
shall be constructed in accordance with paragraph 2.1.1 of appendix
1 and shall be insulated to class "A-60" on the stiffened face, which
shall be the face which is not exposed to the heating conditions of
the test. A deck which includes the pipe penetration shall be constructed
in accordance with paragraph 2.2.1 of appendix 1 and shall be insulated
to class "A-60" on the stiffened face, which shall be the face which
is exposed to the heating conditions of the test.
2.2.1.1 "A-0" class pipe penetrations are recommended
to be performed in an uninsulated ("A-0") bulkhead/deck. If the pipe
penetrations are tested as an "A-60" class penetration, any insulation
fitted (on the penetration itself and 200 mm around) will be required
to be fitted also for class "A-0".
2.2.1.2 "A-0" penetrations shall not be approved
without an "A-0" test although tested and approved as "A-60".
2.2.2 The pipe penetrations shall be positioned
only in the top half of a bulkhead but shall not be closer than 200
mm from the edges of a bulkhead or a deck. Where more than one pipe
penetration is to be tested simultaneously in a division, the separation
between adjacent penetrations shall not be less than 200 mm. Both
measurements shall relate to the distance to the nearest part of the
penetration system, including any insulation which is part of the
system.
2.2.3 Each pipe passing through a penetration
shall project 500 ± 50 mm beyond the exposed end of the penetration
and 500 ± 50 mm beyond the unexposed end of the penetration.
The exposed end of the pipe shall be blanked off, using an appropriate
methodology to ensure that any fire penetration into the pipe does
not occur via the end of the pipe in advance of it occurring through
the exposed perimeter of the pipe.
2.2.4 Each pipe shall be firmly supported and
fixed independent of the bulkhead or deck on the unexposed side of
the test specimen, e.g., by a framework mounted from the restraint
frame. The support and fixing of the pipe shall restrain it from movement
during the test.
2.2.5 When the deck penetration is fitted on an
exposed side or is fitted symmetrically, general application will
be given. When the deck penetration is fitted on an unexposed side,
the approval will limit the penetration to the tested orientation.
2.2.5.1 When the bulkhead penetration is fitted
symmetrically, approval would be given for general application. For
bulkhead penetrations with an exposed or unexposed fitted frame, one
test for each fitting is required in order for obtaining approval
for general application.
2.2.6 Sealing of pipe and duct penetrations: there
shall be no visible openings before the start of the fire test.
2.2.6.1 In cases where a test specimen (deck)
which includes the prototype penetration(s) is not mounted within
a rigid restraint frame but is connected to the furnace roof by side
wall coamings, the rigidity of the coamings is to be equivalent to
that of a restraint frame and evaluated in accordance with paragraph
5.1 of appendix 1.
2.2.6.2 In cases where insulation is fitted to
the test pipe(s), the distance(s) of 500 ± 50 mm required in
paragraph 2.2.3 to which the pipe should project is to be taken from
the end of the insulation as this is considered an integral part of
the penetration(s) being tested and it is necessary that a length
of unprotected pipe is exposed to the furnace.
2.2.6.3 In all cases, the support and fixing of
the test pipe(s) is to be by a framework mounted from the restraint
frame such that any movement of the bulkhead or deck relative to the
pipe(s) will be experienced by the penetration(s) being tested.
3 Instrumentation
3.1 Positioning of thermocouples on the specimen
3.1.1 For each pipe penetration, two thermocouples
shall be fixed on the unexposed face at each of the following locations:
-
.1 on the surface of the pipe at a distance of
25 mm from the centre of the thermocouples to the position where the
pipe emerges from the penetration seal;
-
.2 on the pipe penetration at a distance of 25
mm from the centre of the thermocouples to the face of the insulation
on the unexposed side of the test specimen; and
-
.3 on the surface of any insulation or filling
material used between the pipe and any coaming or spigot fixed to
the division (provided that the gap between the pipe or any such coaming
or spigot is greater than 30 mm), or on the surface of any collar
or shroud used between the pipe and the division (e.g., vapour barrier).
3.1.2 For pipe penetrations in bulkheads, for
each of the positions indicated above, one of the thermocouples shall
be fixed directly above the centre of the pipe and the other thermocouple
shall be fixed directly below the centre of the pipe.
3.1.3 Additional thermocouples may be required
to be fitted, dependent upon the complexity of the pipe penetration.
4 Performance Criteria
4.1 General
4.1.1 The performance of pipe penetrations may
be related to their ability to satisfy both the insulation and the
integrity criteria or may be related only to the requirements for
integrity, depending on the requirements of the Administration.
4.1.2 Duct penetrations shall meet both integrity
and insulation criteria.
4.2 Insulation
Since the pipe penetration is a local weakness in the division
it shall be capable of preventing a temperature rise exceeding l80°C
above the initial temperature. The average temperature rise is not
relevant.
A.IV – Cable Transits
1 General
"A" class divisions may have to be provided with apertures
to allow them to be penetrated by cables, and it is necessary to reinstate
the insulation and integrity performance of the division at the position
where it has been penetrated. A cable transit consists of a metal
frame, box or coaming, a sealant system or material and the cables,
and it may be uninsulated, partially insulated or fully insulated.
2 Nature of the Test Specimen
2.1 Dimensions
The maximum and minimum sizes (in terms of both the height
and the width) of each type of cable transit for which approval is
sought shall be tested in both vertical and horizontal orientation.
2.2 Design
2.2.1 A bulkhead which includes the cable transit
shall be constructed in accordance with paragraph 2.1.1 of appendix
1 and shall be insulated to class "A-60" on the stiffened face, which
shall be the face which is not exposed to the heating conditions of
the test. A deck which includes the cable transit shall be constructed
in accordance with paragraph 2.2.1 of appendix 1 and shall be insulated
to class "A-60" on the stiffened face, which shall be the face which
is exposed to the heating conditions of the test.
2.2.1.1 "A-0" class cable transits are recommended
to be performed in an uninsulated ("A-0") bulkhead/deck. If the cable
transits are tested as "A-60" penetration, any insulation fitted on
an exposed side (on the cable transits itself and 200 mm around) will
be required to be fitted also for "A-0".
2.2.1.2 "A-0" cable transits shall not be approved
without an "A-0" test although tested and approved as "A-60".
2.2.2 The cable transits shall be positioned only
in the top half of a bulkhead but shall not be closer than 200 mm
from the edges of a bulkhead or a deck. Where more than one cable
transit is to be tested simultaneously in a division, the separation
between adjacent transits shall not be less than 200 mm. Both measurements
shall relate to the distance to the nearest part of the transit system,
including any insulation which is part of the system.
2.2.3 Notwithstanding the above, the distance
between transits shall be sufficient to ensure that the transits do
not influence each other during the test, except that this requirement
does not apply to multi-transits which are intended to be positioned
adjacent to one another.
2.2.4 The cables shall project 500 ± 50
mm beyond the transit on the exposed side of the division and 500
± 50 mm on the unexposed side.
2.2.4.1 Each cable shall be firmly supported and
fixed independent of the bulkhead or deck on the unexposed side of
the test specimen, e.g., by a framework mounted from the restraint
frame. The support and fixing of the cables shall restrain them from
movement during the test.
2.2.5 Cable transits shall be fitted to the bulkhead
or deck in accordance with the manufacturer's specifications. The
cables and sealing compounds or blocks shall be incorporated into
the transits with the bulkhead and deck panels placed respectively
in vertical and horizontal positions. Any insulation shall be applied
to the cables and transits with the panels in the same respective
positions.
2.2.6 The transit(s) shall be tested incorporating
a range of different types of cables (e.g., in terms of number and
type of conductor, type of sheathing, type of insulation material,
size) and shall provide an assembly which represents a practical situation
which may be found on ships. An individual Administration may have
its own specification for a "standard" configuration of penetrating
cables which it may use as a basis of its approvals.
2.2.6.1 The test results obtained from a given
configuration are generally valid for the tested types of cables of
size equal to or smaller than tested.
2.2.7 Tests shall be conducted for the maximum
and minimum fill based on the inside cross-sectional area at each
transit. The distance between the adjacent cables shall be the minimum
specified by the manufacturer, and the cables should be placed close
to the centre of the transit.
2.2.8 When the deck cable transit is fitted on
an exposed side or is fitted symmetrically, general application will
be given. When the deck cable transit is fitted on the unexposed side,
the approval will limit the penetration to the tested orientation.
2.2.8.1 When the bulkhead cable transit is fitted
symmetrically, approval would be given for general application. For
bulkhead cable transit with exposed or unexposed fitted frame, one
test for each fitting is required in order for obtaining approval
for general application.
2.2.9 Sealing of cable transits shall have no
visible openings before the start of the fire test
3 Instrumentation
3.1 Positioning of thermocouples on the specimen
3.1.1 For each uninsulated cable transit, thermocouples
shall be fixed on the unexposed face at each of the following locations:
-
.1 at two positions on the surface of the frame,
box or coaming at a distance of 25 mm from the unexposed surface of
the division. When the penetration does not extend a minimum of 25
mm beyond the bulkhead or deck plate on the unexposed side of the
assembly, these thermocouples shall be placed at the end of the frame,
box or coaming;
-
.2 at two positions at the end of the transit,
on the face of the sealant system or material at a distance of 25
mm from a cable. If there is insufficient area to affix the thermocouples
as described, one or both may be placed within a distance of 25 mm
from a cable; and
-
.3 on the surface of each type of cable included
in the cable transit, at a distance of 25 mm from the face of the
sealant system or material. In case of a group or bunch of cables,
the group shall be treated as a single cable. In case of horizontal
cables, the thermocouples shall be mounted on the uppermost surface
of the cables. These thermocouples may be excluded if the diameters
of the cables are too small to effectively affix the thermocouples
to the cables. This shall be at the discretion of the Administration.
3.1.2 For those thermocouples placed on the outer
perimeter of the frame, box or coaming, one thermocouple shall be
fixed on each of two opposite faces, which in the case of bulkheads
shall be the top and bottom faces.
3.1.3 For each partially insulated or fully insulated
cable transit, thermocouples shall be fixed on the unexposed face
at equivalent positions to those specified for an uninsulated transit
as illustrated in figure A2.
3.1.4 Additional thermocouples may be required
to be fixed, dependent upon the complexity of the cable transit.
3.1.5 When fixing thermocouples to the unexposed
surface of the cables, the copper disc and the insulating pad shall
be formed over the surface to provide good contact with the surface
of the cable. The copper disc and the pad shall be retained in position
by some mechanical means, e.g., wiring or spring clips, such that
they do not become detached during the test. The mechanical retention
shall not provide any significant heat-sink effect to the unexposed
face of the thermocouple.
4 Performance Criteria
4.1 General
Cable transits shall meet both integrity and insulation
criteria.
4.2 Insulation
Since the cable transit is a local weakness in the division,
the temperature rise at any point on the surface shall not exceed
180°C above the initial temperature. The average temperature rise
shall not be used for this purpose.
|