6.6.1 Electrical equipment and wiring installed
in hazardous areas should be limited to that necessary for operational
purposes. Only the cables and types of equipment described in this
Chapter may be installed.
6.6.2 Where, in the following, reference is made
to certified types of equipment, such equipment should be certified
as suitable for the flammable gas/air mixture which may be encountered.footnote
6.6.3 Cables and types of electrical equipment
permitted in hazardous areas are as follows:
6.6.4 Permanently installed, fixed cables passing
through Zone 1 hazardous areas should be fitted with a conductive
covering, braiding or sheath for earth detection. Flexible cables
passing through such areas should be to the satisfaction of the Administration.