(1) In vessels in which method IIF is adopted
an automatic sprinkler and fire alarm system of an approved type and
complying with the requirements of this regulation shall be installed
and so arranged as to protect accommodation spaces and service spaces
except spaces which afford no substantial fire risks, such as void
spaces and sanitary spaces.
(2)
-
(a) The system shall be capable of immediate operation
at all times and no action by the crew shall be necessary to set it
in operation. It shall be of the wet pipe type but small exposed sections
may be of the dry pipe type where in the opinion of the Administration
this is a necessary precaution. Any parts of the system which may
be subjected to freezing temperatures in service shall be suitably
protected against freezing.footnoteIt shall
be kept charged at the necessary pressure and shall have provision
for a continuous supply of water as required in paragraph (6)(b).
-
(b) Each section of sprinklers shall include means
for giving a visible and audible alarm signal automatically at one
or more indicating units whenever any sprinkler comes into operation.
Such units shall indicate in which section served by the system, fire
has occurred and shall be centralized in the wheelhouse and, in addition,
visible and audible alarms from the unit shall be placed in a position
other than in the wheel house, so as to ensure that the indication
of fire is immediately received by the crew. Such an alarm system
shall be so constructed as to indicate if any fault occurs in the
system.
(3)
-
(a) Sprinklers shall be grouped into separate
sections, each of which shall contain not more than 200 sprinklers.
-
(b) Each section of sprinklers shall be capable
of being isolated by one stop valve only. The stop valve in each section
shall be readily accessible and its location shall be clearly and
permanently indicated. Means shall be provided to prevent the operation
of the stop valves by any unauthorised person.
-
(c) A gauge indicating the pressure in the system
shall be provided at each section stop valve and at a central station.
-
(d) The sprinklers shall be resistant to corrosion
In accommodation and service spaces the sprinklers shall come into
operation within the temperature range of 68°C and 79°C, except
that in locations such as drying rooms, where high ambient temperatures
might be expected, the operating temperature may be increased by not
more than 30°C above the maximum deck head temperature.
-
(e) A list or plan shall be displayed at each
indicating unit showing the spaces covered and the location of the
zone in respect of each section. Suitable instructions for testing
and maintenance shall be available.
(4) Sprinklers shall be placed in an overhead
position and spaced in a suitable pattern to maintain an average application
rate of not less than 5 l/m2/min over the
nominal area covered by the sprinklers. Alternatively, the Administration
may permit the use of sprinklers providing such quantity of water
suitably distributed as has been shown to the satisfaction of the
Administration to be not less effective.
(5)
-
(a) A pressure tank having a volume equal to at
least twice that of the charge of water specified in this subparagraph
shall be provided. The tank shall contain a standing charge of fresh
water, equivalent to the amount of water which would be discharged
in one minute by the pump referred to in paragraph (6)(b), and the
arrangements shall provide for maintaining such air pressure in the
tank as to ensure that, where the standing charge of fresh water in
the tank has been used, the pressure will be not less than the working
pressure of the sprinkler, plus the pressure due to a head of water
measured from the bottom of the tank to the highest sprinkler in the
system. Suitable means of replenishing the air under pressure and
of replenishing the fresh water charge in the tank shall be provided.
A glass gauge shall be provided to indicate the correct level of the
water in the tank.
-
(b) Means shall be provided to prevent the passage
of seawater into the tank.
(6)
-
(a) An independent power pump shall be provided
solely for the purpose of continuing automatically the discharge of
water from the sprinklers. The pump shall be brought into action automatically
by the pressure drop in the system before the standing fresh water
charge in the pressure tank is completely exhausted.
-
(b) The pump and the piping system shall be capable
of maintaining the necessary pressure at the level of the highest
sprinkler to ensure a continuous output of water sufficient for the
simultaneous coverage of the maximum area separated by fire-resisting
bulkheads of "A" and "B" class divisions or an area of 280 m2 whichever
is the less at the application rate specified in paragraph (4).
-
(c) The pump shall have fitted on the delivery
side a test valve with a short open-ended discharge pipe. The effective
area through the valve and pipe shall be adequate to permit the release
of the required pump output while maintaining the pressure in the
system specified in paragraph (5)(a).
-
(d) The sea inlet to the pump shall wherever possible
be in the space containing the pump and shall be so arranged that
when the vessel is afloat it will not be necessary to shut off the
supply of seawater to the pump for any purpose other than the inspection
or repair of the pump.
(7) The sprinkler pump and tank shall be situated
in a position reasonably remote from any machinery space of category
A and shall not be situated in any space required to be protected
by the sprinkler system.
(8)
-
(a) There shall not be less than two sources of
power supply for the seawater pump and the automatic fire alarm and
fire detection system. If the pump is electrically driven it shall
be connected to the main source of electrical power, which shall be
capable of being supplied by at least two generators.
-
(b) The feeders shall be arranged so as to avoid
galleys, machinery spaces and other enclosed spaces of high fire risk
except in so far as it is necessary to reach the appropriate switchboard.
One of the sources of power supply for the fire alarm and fire detection
system shall be an emergency source. Where one of the sources of power
for the pump is an internal combustion-type engine it shall, in addition
to complying with the provisions of paragraph (7), be so situated
that a fire in any protected space will not affect the air supply
to that engine.
(9) The sprinkler system shall have a connection
from the vessel's fire main by way of a lockable screw-down nonreturn
valve at the connection which will prevent a backflow from the sprinkler
system to the fire main.
(10)
-
(a) A test valve shall be provided for testing
the automatic alarm for each section of sprinklers by a discharge
of water equivalent to the operation of one sprinkler. The test valve
for each section shall be situated near the stop valve for that section.
-
(b) Means shall be provided for testing the automatic
operation of the pump on reduction of pressure in the system.
-
(c) Switches shall be provided at one of the indicating
positions referred to in paragraph (2)(b) which will enable the alarm
and the indicators for each section of sprinklers to be tested.
(11) Spare sprinkler heads shall be provided for
each section of sprinklers to the satisfaction of the Administration.