Appendix 2 – Fire Test Procedures for Toxic Gas Generation
1 Scope
1.1 This appendix specifies methods of measurement
of gases developed in cumulative smoke/fire test, using Fourier transform
infrared spectroscopy (FTIR). Particular attention is given to the
gas sampling systems and conditions of gas measurement.
1.2 It should be noted that there are fire effluents
other than gases, such as particles, smoke or vapours, which may be
toxic and that some gases such as hydrogen halides may be trapped
by moisture in sampling lines or by filters designed to remove only
smoke particles.
1.3 Gas measurements by FTIR shall be carried
out when the maximum smoke density is obtained. That time is determined
by a smoke density measurement tests carried out in accordance with
appendix 1.
2 Normative References
The following normative documents contain provisions which
constitute provisions of this appendix:
-
ISO 5659-2, Plastics – Smoke generation – Part
2: Determination of optical density by a single-chamber test.
-
ISO 13943, Fire safety – Vocabulary.
-
ISO 19702, Toxicity testing of fire effluents – Analysis
of gases and vapours in fire effluents using FTIR technology.
3 Terms and Definitions
For the purposes of this document, the terms and definitions
given in standards ISO 13943 and ISO 19702 and the following apply.
3.1
Maximum smoke density sampling time
(DmST) is the sampling time, expressed in seconds, used in
toxicity tests correspondent to the time to reach the maximum specific
optical density as per paragraph 2.4.1 of part 2.
3.2
Sampling Response Period (SRP) is
the minimum time necessary during the sampling period to completely
load the FTIR gas cell including the time to transfer the effluents
flow from the smoke chamber into the cell.
4 Principles
Fire effluents are sampled from a cumulative smoke chamber
of a smoke test (appendix 1) at a single time point called Dm sampling
time (DmST) which is pre-determined by the first smoke density test
in appendix 1. This time represents the time where the smoke density
reaches the maximum level during the standard 20 min test. Gas sampling
shall be such that the sample represents the gas, the fire effluent,
in quality and quantity, in the chamber, and that any effect of gas
sampling systems (filters, probes, pipes, tubes and pumps) in minimized.
It is recommended to minimize the travelling time and distance of
fire effluent through the gas sampling system. A filtering system
for fire effluent shall be installed within the gas sampling system
to prevent smoke particles from entering into the gas analyser. FTIR
shall be used to analyse the sampled gases.
5 Gas Sampling System
Gas sampling system should consist of probe, heated gas
sampling line, filter, valves and sampling pump.
6 Gas Analysis Technique
An FTIR system as described in standard ISO 19702 shall
be used.
7 Calibration
Calibration of the FTIR system shall be carried out for
gases to be measured in accordance with standard ISO 19702.
8 Test Procedures
8.1 Operation before each test
8.1.1 Check the internal walls condition of the
test chamber and eventually clean them removing all dirty layers and
particles. The same operation shall be done on the surface of the
internal probe for FTIR sampling.
8.1.2 The inlet of the probe shall be cleaned.
8.1.3 Keep the filter, gas sampling line and valves
and gas cell at the temperature of 150°C to 180°C for at least
10 min prior to the test.
8.1.4 The wavelength resolution of the spectrometer
shall be 4 cm-1 or better. Set the Mid-IR whole spectral
region for collection between 650 cm-1 to 4,500 cm-1.
8.1.5 Close the chamber door, and introduce the
air in the chamber into the gas cell of FTIR. Wait for 1 min and record
the background spectrum.
8.1.6 Turn the sampling valve to introduce the
open air into the gas cell.
-
Note: It is recommended, before the start of any
smoke test on that day, to carry out a dummy gas measurement where
the ambient air in the smoke chamber is sampled and analysed by the
normal test procedure, and to make sure that no gas is detected. It
is also recommended that such a dummy gas measurement be carried out
whenever a questionable gas measurement result is obtained. It is
also recommended that this screening measurement be carried out after
the smoke chamber is cleaned by volatile solvent.
8.2 Operation during a test
8.2.1 During the smoke density test specified
in appendix 1, the sampling shall start by turning the sampling valve
to introduce gas in the chamber into the sampling line, at DmST
– (SRP x 0.5) (s).
8.2.2 Wait for a minimum period equal to SRP then
collect the spectrum, stop the sampling from the chamber and turn
the sampling valve to introduce open air side.
8.2.3 Continue the smoke density test until a
20 min period has elapsed. To verify the end of the test, ensure that
the smoke density peak has already occurred.
8.2.4 At the end of the test, follow the end of
the test procedures described in appendix 1.
8.2.5 If the smoke chamber pressure drops below
the permitted minimum as specified in standard ISO 5659-2 by any phenomena
of the combustion of the specimen, the gas inlet valve of the chamber
will automatically open according to standard ISO 5659-2. If this
happens, this shall be reported.
8.2.6 If the smoke chamber pressure exceeds the
permitted maximum as specified in standard ISO 5659-2 by any phenomena
of the combustion of the specimen, the gas release valve of the chamber
will automatically open according to standard ISO 5659-2. If this
happens, this shall be reported.
8.3 Repeat tests
In case an additional set of three smoke measurement tests
are repeated in accordance with appendix 1, paragraph 8.8.2, in any
of the test conditions in paragraph 8.8.1 of appendix 1, gas measurements
shall be conducted at the second and third test of the second set
of the tests in accordance with this appendix and the test results
shall be reported in accordance with paragraph 10.
9 Gas Analysis
9.1 FTIR gas analysis
FTIR gas analysis shall be carried out in accordance with
standard ISO 19702.
9.2 Calculation of concentration correction for
acid gases
9.2.1 Analysis of filtering materials used in
the gas sampling line shall be carried out, and total acid gases trapped
by the filtering materials (Qa (g)) shall be obtainedfootnote.
9.2.2 The relative concentration shall be calculated
based on the total gas volume (Vs (l)) passing through the filter
for the gas sampling period:
Where:
9.2.3 Relative volume of the gas (Va (l)) shall be calculated by:
where:
9.2.4 The concentration correction (Cca (ppm))
for an acid gas shall be obtained by:
10 Test Results
The following test results shall be included in the test
report:
-
.1 for each test:
-
.1 maximum gas concentration C (ppm) measured
by FTIR for each gas listed in paragraph 2.4.2 of this part;
-
.2 gas concentration correction (Cca),
if applicable;
-
.3 corrected maximum gas concentration (C
+ Cca), if applicable; and
-
.4
DmST and SRP;
-
.2 for each test condition (see paragraph 8.8.1
of appendix 1), the average value of the maximum value of the gas
concentration measured and corrected, if applicable, at each test
condition; and
-
.3 data regarding the test apparatus:
-
.1 the inner volume of the gas cell;
-
.2 the inner volume and the length of gas sampling
line; and
-
.3 the capacity of the gas sampling pump.
|
Copyright 2022 Clasifications Register Group Limited, International Maritime Organization, International Labour Organization or Maritime
and Coastguard Agency. All rights reserved. Clasifications Register Group Limited, its affiliates and subsidiaries and their respective
officers, employees or agents are, individually and collectively, referred to in this clause as 'Clasifications Register'. Clasifications
Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance
on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant
Clasifications Register entity for the provision of this information or advice and in that case any responsibility or liability is
exclusively on the terms and conditions set out in that contract.
|
|
|