3.1 In case any one main vertical zone is unserviceable
due to fire, the following systems shall be so arranged and segregated
as to remain operational:
-
.1 fire main;
-
.2 internal communications (in support of fire-fighting
as required for passenger and crew notification and evacuation);
-
.3 means of external communications;
-
.4 bilge systems for removal of fire-fighting
water;
-
.5 lighting along escape routes, at assembly stations
and at embarkation stations of life-saving appliances; and
-
.6 guidance systems for evacuation shall be available.
3.2 The above systems shall be capable of operation
for at least 3 h based on the assumption of no damage outside the
unserviceable main vertical zone. These systems are not required to
remain operational within the unserviceable main vertical zones.
3.3 Cabling and piping within a trunk constructed
to an "A-60" standard shall be deemed to remain intact and serviceable
while passing through the unserviceable main vertical zone for the
purposes of paragraph 3.1. An equivalent degree of protection for
cabling and piping may be approved by the Administration.