7.7 Fire detection and extinguishing
systems
7.7.1 Fire detection systems
Areas of major and moderate fire hazard and other enclosed
spaces not regularly occupied within public spaces and crew accommodation,
such as toilets, stairway enclosures, corridors and escape routes
shall be provided with an approved automatic smoke-detection system
and manually operated call points complying with the requirements
of 7.7.1.1 and 7.7.1.3 to indicate at the control station the location
of outbreak of a fire in all normal operating conditions of the installations.
Control stations not normally occupied (e.g., emergency generator
rooms) need not be provided with manually operated call points. Detectors
operated by heat instead of smoke may be installed in galleys. Main
propulsion machinery room(s) shall in addition have detectors sensing
other than smoke and be supervised by TV cameras monitored from the
operating compartment. Manually operated call points shall be installed
throughout the public spaces, crew accommodation, corridors and stairway
enclosures, service spaces and, where necessary, control stations.
One manually operated call point shall be located at each exit from
these spaces and from areas of major fire hazard.
7.7.1.1 General requirements
-
.1 Any required fixed fire-detection and fire
alarm system with manually operated call points shall be capable of
immediate operation at all times.
-
.2 Power supplies and electric circuits necessary
for the operation of the system shall be monitored for loss of power
or fault conditions as appropriate. Occurrence of a fault condition
shall initiate a visual and audible fault signal at the control panel
which shall be distinct from a fire signal.
-
.3 There shall be not less than two sources of
power supply for the electrical equipment used in the operation of
the fixed fire-detection and fire alarm system, one of which shall
be an emergency source. The supply shall be provided by separate feeders
reserved solely for that purpose. Such feeders shall run to an automatic
change-over switch situated in or adjacent to the control panel for
the fire-detection system.
-
.4 Detectors and manually operated call points
shall be grouped into sections, each of which shall comprise a group
of fire detectors and manually operated call points as displayed at
the indicating unit(s) required by this paragraph. The activation
of any detector or manually operated call point shall initiate a visual
and audible fire signal at the control panel and indicating units.
If the signals have not received attention within two minutes an audible
alarm shall be automatically sounded throughout the crew accommodation
and service spaces, control stations and machinery spaces. There shall
be no time delay for the audible alarms in crew accommodation areas
when all the control stations are unattended. The alarm sounder system
need not be an integral part of the detection system.
-
.5 The control panel shall be located in the operating
compartment or in the main fire control station.
-
.6 Indicating units shall, as a minimum, denote
the section in which a detector or manually operated call point has
operated. At least one unit shall be so located that it is easily
accessible to responsible members of the crew at all times, when at
sea or in port, except when the craft is out of service. One indicating
unit shall be located in the operating compartment if the control
panel is located in the space other than the operating compartment.
-
.7 Clear information shall be displayed on or
adjacent to each indicating unit about the spaces covered and the
location of the sections.
-
.8 Where the fire-detection system does not include
means of remotely identifying each detector individually, no section
covering more than one deck within public spaces, crew accommodation,
corridors, service spaces and control stations shall normally be permitted
except a section which covers an enclosed stairway. In order to avoid
delay in identifying the source of fire, the number of enclosed spaces
included in each section shall be limited as determined by the Administration.
In no case shall more than 50 enclosed spaces be permitted in any
section. If the detection system is fitted with remotely and individually
identifiable fire detectors, the sections may cover several decks
and serve any number of enclosed spaces.
-
.9 In passenger craft, if there is no fire-detection
system capable of remotely and individually identifying each detector,
a section of detectors shall not serve spaces on both sides of the
craft nor on more than one deck and neither shall it be situated in
more than one zone according to 7.11.1.
In passenger craft fitted with individually identifiable fire detectors,
a section may serve spaces on both sides of the craft and on several
decks. Notwithstanding the preceding requirements of this paragraph,
the Administration may accept that the same section of detectors can
serve spaces on more than one deck if such spaces are located in the
fore or aft end of the craft or they are so arranged that they constitute
common spaces on different decks (e.g., fan rooms, galleys, public
spaces, etc.).
-
.10 A section of fire detectors which covers a
control station, a service space, a public space, crew accommodation,
corridor or stairway enclosure shall not include a machinery space
of major fire hazard. In the case of a fire detection system with
remotely and individually identifiable fire detectors, this requirement
is met if no machinery spaces of a major fire hazard are included
in a loop (electrical circuit linking detectors of various sections
in a sequence and connected (input and output) to the indicating unit(s))
covering accommodation spaces, service spaces and control stations.
-
.11 Detectors shall be operated by heat, smoke
or other products of combustion, flame, or any combination of these
factors. Detectors operated by other factors indicative of incipient
fires may be considered by the Administration provided that they are
no less sensitive than such detectors. Flame detectors shall only
be used in addition to smoke or heat detectors.
-
.12 Suitable instructions and component spares
for testing and maintenance shall be provided.
-
.13 The function of the detection system shall
be periodically tested by means of equipment producing hot air at
the appropriate temperature, or smoke or aerosol particles having
the appropriate range of density or particle size, or other phenomena
associated with incipient fires to which the detector is designed
to respond. All detectors shall be of a type such that they can be
tested for correct operation and restored to normal surveillance without
the renewal of any component.
-
.14 The fire-detection system shall not be used
for any other purpose, except that the control panel may be used to
activate one or more of the following:
-
.15 Fire detection systems in which all fire detectors
are individually identifiable (i.e. having zone address identification
capability) shall be so arranged that:
-
.1 a loop cannot be damaged at more than one point
by a fire and no loop shall pass through a space twice. When this
is not practical (e.g., for large public spaces), the part of the
loop which by necessity passes through the space for a second time
shall be installed at the maximum possible distance from the other
parts of the loop;
-
.2 means are provided to ensure that any fault
(e.g., power break; short circuit; earth) occurring in the loop shall
not render the whole loop ineffective;
-
.3 all arrangements are made to enable the initial
configuration of the system to be restored in the event of failure
(electrical, electronic, informatic); and
-
.4 the first initiated fire alarm shall not prevent
any other detector to initiate further fire alarms.
-
.16 The fire detection system in vehicle deck
spaces, excluding manual call points, may be switched off with a timer
during loading/unloading of vehicles.
7.7.1.2 Installation requirements
-
.1 In addition to 7.7.1,
manually operated call points shall be readily accessible in the corridors
of each deck such that no part of the corridor is more than 20 m from
a manually operated call point.
-
.2 Where a fixed fire-detection and fire alarm
system is required for the protection of spaces other than stairways,
corridors and escape routes, at least one detector complying with 7.7.1.1.11 shall be installed in each
such space.
-
.3 Detectors shall be located for optimum performance.
Positions near beams and ventilation ducts or other positions where
patterns of air flow could adversely affect performance and positions
where impact or physical damage is likely shall be avoided. Detectors
which are located in the overhead shall be a minimum distance of 0.5
m away from bulkheads, except in corridors, lockers and stairways.
-
.4 The maximum spacing of detectors shall be in
accordance with the table below:
Type of detector
|
Maximum floor area per detector
|
Maximum distance apart between centres
|
Maximum distance away from bulkheads
|
Heat
|
37 m2
|
9 m
|
4.5 m
|
Smoke
|
74 m2
|
11 m
|
5.5 m
|
The Administration may require or permit other
spaces based upon test data which demonstrate the characteristics
of the detectors.
-
.5 Electrical wiring which forms parts of the
system shall be so arranged as to avoid machinery spaces of major
fire hazard, and other enclosed spaces of major fire hazard except,
where it is necessary, to provide for fire detection or fire alarm
in such spaces or to connect to the appropriate power supply.
7.7.1.3 Design requirements
-
.1 The system and equipment shall be suitably
designed to withstand supply voltage variation and transients, ambient
temperature changes, vibration, humidity, shock, impact and corrosion
normally encountered in ships.
-
.2 Smoke detectors shall be certified to operate
before the smoke density exceeds 12.5% obscuration per metre, but
not until the smoke density exceeds 2% obscuration per metre. Smoke
detectors to be installed in other spaces shall operate within sensitivity
limits to the satisfaction of the Administration having regard to
the avoidance of detector insensitivity or over-sensitivity.
-
.3 Heat detectors shall be certified to operate
before the temperature exceeds 78°C but not until the temperature
exceeds 54°C, when the temperature is raised to those limits at
a rate less than 1°C per minute. At higher rates of temperature
rise, the heat detector shall operate within temperature limits having
regard to the avoidance to detector insensitivity or over-sensitivity.
-
.4 At the discretion of the Administration, the
permissible temperature of operation of heat detectors may be increased
to 30°C above the maximum deckhead temperature in drying rooms
and similar spaces of a normal high ambient temperature.
-
.5 Flame detectors corresponding to 7.7.1.1.11 shall have a sensitivity sufficient
to determine flame against an illuminated space background and a false
signal identification system.
7.7.2 Fire detection for periodically
unattended machinery spaces
A fixed fire-detection and fire alarm system for periodically
unattended machinery spaces shall comply with the following requirements:
-
.1 The fire-detection system shall be so designed
and the detectors so positioned as to detect rapidly the onset of
fire in any part of those spaces and under any normal conditions of
operation of the machinery and variations of ventilation as required
by the possible range of ambient temperatures. Except in spaces of
restricted height and where their use is specially appropriate, detection
systems using only thermal detectors shall not be permitted. The detection
system shall initiate audible and visual alarms distinct in both respects
from the alarms of any other system not indicating fire, in sufficient
places to ensure that the alarms are heard and observed on the navigating
bridge and by a responsible engineer officer. When the operating compartment
is unmanned the alarm shall sound in a place where a responsible member
of the crew is on duty.
-
.2 After installation, the system shall be tested
under varying conditions of engine operation and ventilation.
7.7.3 Fixed fire-extinguishing
systems
7.7.3.1 Areas of major fire hazard shall be protected
by an approved fixed fire-extinguishing system operable from the operating
compartment and, where provided, from a control position which is
adequate for the fire hazard that may exist. The system shall comply
with 7.7.3.2 and 7.7.3.3 or with alternative arrangements approved
by the Administration taking into account the recommendations and
guidelines developed by the Organization,footnote and
be capable of local manual control and remote control from the continuously
manned control stations.
7.7.3.2 Additional fixed fire-extinguishing systems
not required by the Code, but fitted to the craft are to meet the
design requirements of this Code, except for the second discharge
required for fixed gas fire-extinguishing systems.
7.7.3.3 General requirements
-
.1 In all craft where gas is used as the extinguishing
medium, the quantity of gas shall be sufficient to provide two independent
discharges. The second discharge into the space shall only be activated
manually from a position outside the space being protected. Where
the space has a local fire-suppression system installed, based on
the guidelines developed by the Organization,footnote to
protect fuel oil, lubricating oil and hydraulic oil located near exhaust
manifolds, turbo chargers or similar heated surfaces on main and auxiliary
internal combustion engines, a second discharge need not be required.
-
.2 The use of a fire-extinguishing medium which,
in the opinion of the Administration, either by itself or under expected
conditions of use will adversely affect the earth's ozone layer and/or
gives off toxic gases in such quantities as to endanger persons shall
not be permitted.
-
.3 The necessary pipes for conveying fire-extinguishing
medium into protected spaces shall be provided with control valves
so marked as to indicate clearly the spaces to which the pipes are
led. Pipelines may pass through accommodation spaces, provided they
are of substantial thickness and their tightness is verified with
a pressure test, after their installation, at a pressure head not
less than 5 N/mm2. In addition, pipelines passing through
accommodation areas shall only be joined by welding and shall not
be fitted with drains or other openings within such spaces. Pipelines
shall not pass through refrigerated spaces. Non-return valves shall
be installed in discharge lines between cylinders and manifolds. Suitable
provision shall be made to prevent inadvertent admission of the medium
to any space.
-
.4 The piping for the distribution of fire-extinguishing
medium shall be arranged and discharge nozzles so positioned that
a uniform distribution of medium is obtained.
-
.5 Means shall be provided to close all openings
which may admit air to, or allow gas to escape from, a protected space.
Openings that may admit air to, or allow gas to escape from, a protected
space shall be capable of being closed from outside the protected
space.
-
.6 Where the volume of free air contained in air
receivers in any space is such that, if released in such space in
the event of fire, such release of air within that space would seriously
affect the efficiency of the fixed fire-extinguishing system, the
Administration shall require the provision of an additional quantity
of fire-extinguishing medium corresponding to the gross volume of
the machinery space being increased by the volume of air receivers
converted to free air volume. Alternatively, a discharge pipe connected
to a safety valve may be fitted to each air receiver, provided it
leads directly to the open air.
-
.7 Means shall be provided for automatically giving
audible warning of the release of fire-extinguishing medium into any
space in which personnel normally work or which personnel can be expected
to enter (e.g., ro-ro spaces) and where their access is facilitated
by doors or hatches or to which they have access. The alarm shall
automatically operate (e.g., by opening of the release cabinet door)
for a suitable period before the medium is released, but not less
than 20 s. A visible alarm shall be arranged in addition to the audible
alarm.footnote
-
.8 The means of control of any fixed gas fire-extinguishing
system shall be readily accessible and simple to operate and shall
be grouped together in as few locations as possible at positions not
likely to be cut off by a fire in a protected space. At each location
there shall be clear instructions relating to the operation of the
system, having regard to the safety of personnel.
-
.9 Automatic release of fire-extinguishing medium
shall not be permitted.
-
.10 Where the extinguishing medium is required
to protect more than one space, the quantity of medium available need
not be more than the largest quantity required for any one space so
protected. Spaces are considered as separated where divisions comply
with tables 7.4-1 and 7.4-2, as appropriate, or the divisions
are gastight and of steel or equivalent materials.
-
.11 Pressure containers required for the storage
of fire-extinguishing medium shall be located outside protected spaces
in accordance with 7.7.3.3.14. Pressure containers may be located
inside the space to be protected if in the event of accidental release
persons will not be endangered.
-
.12 Means shall be provided for the crew to safely
check the quantity of medium in the containers without moving the
containers completely from their fixing position.
-
.13 Containers for the storage of fire-extinguishing
medium and associated pressure components shall be designed having
regard to their locations and maximum ambient temperatures expected
in service.
-
.14 When the fire-extinguishing medium is stored
outside a protected space, it shall be stored in a room which shall
be situated in a safe and readily accessible location. For the purpose
of the application of tables 7.4-1 and 7.4-2, such storage rooms shall
be treated as control stations. For the storage rooms for fire-extinguishing
media of fixed gas fire-extinguishing systems, the following apply:
-
.1 the storage room shall not be used for any
other purposes;
-
.2 if the storage space is located below deck,
it shall be located no more than one deck below the open deck and
shall be directly accessible by a stairway or ladder from the open
deck;
-
.3 spaces shall be effectively ventilated. Spaces
which are located below deck or spaces where access from the open
deck is not provided, shall be fitted with a mechanical ventilation
system designed to take exhaust air from the bottom of the space and
shall be sized to provide at least 6 air changes per hour; and
-
.4 access doors shall open outwards, and bulkheads
and decks including doors and other means of closing any opening therein,
which form the boundaries between such rooms and adjacent enclosed
spaces shall be gastight.
-
.15 Spare parts for the system shall be stored
on board or at a base port.
-
.16 If the release of a fire extinguishing medium
produces significant over- or under-pressurisation in the protected
space, means shall be provided to limit the induced pressures to acceptable
limits to avoid structural damage.
7.7.3.4 Carbon dioxide systems
-
.1 For cargo spaces, the quantity of carbon dioxide
available shall, unless otherwise provided, be sufficient to give
a minimum volume of free gas equal to 30% of the gross volume of the
largest cargo space so protected in the craft.
-
.2 For machinery spaces, the quantity of carbon
dioxide carried shall be sufficient to give a minimum volume of free
gas equal to the larger of the following volumes, either:
-
.2.1 40% of the gross volume of the largest machinery
space so protected, the volume to exclude that part of the casing
above the level at which the horizontal area of the casing is 40%
or less of the horizontal area of the space concerned taken midway
between the tank top and the lowest part of the casing; or
-
.2.2 35% of the gross volume of the largest machinery
space protected, including the casing;
provided that
the above-mentioned percentages may be reduced to 35% and 30% respectively
for cargo craft of less than 2,000 gross tonnage; provided also that
if two or more machinery spaces are not entirely separate they shall
be considered as forming one space.
-
.3 For the purpose of this paragraph the volume
of free carbon dioxide shall be calculated at 0.56 m3/kg.
-
.4 For machinery spaces, the fixed piping system
shall be such that 85% of the gas can be discharged into the space
within 2 min.
-
.5 Two separate controls shall be provided for
releasing carbon dioxide into a protected space and to ensure the
activation of the alarm. One control shall be used to discharge the
gas from its storage containers. A second control shall be used for
opening the valve of the piping which conveys the gas into the protected
spaces.
-
.6 The two controls shall be located inside a
release box clearly identified for the particular space. If the box
containing the controls is to be locked, a key to the box shall be
in a break-glass type enclosure conspicuously located adjacent to
the box.
7.7.4 Portable fire extinguishers
footnote
Control stations, public spaces, crew accommodation, corridors
and service spaces shall be provided with portable fire extinguishers
of approved type and design. At least five portable extinguishers
shall be provided and so positioned as to be readily available for
immediate use. In addition, at least one extinguisher suitable for
machinery space fires shall be positioned outside each machinery space
entrance. Each portable fire extinguisher shall:
-
.1 not exceed 23 kg in total mass;
-
.2 have a capacity of at least 5 kg if of powder
or carbon dioxide type;
-
.3 have a capacity of at least 9 l if of
foam type;
-
.4 be examined annually;
-
.5 be provided with a sign indicating the date
when was last examined;
-
.6 be hydraulic-pressure tested (cylinders and
propellant bottles) every 10 years;
-
.7 not be placed in accommodation spaces if of
carbon dioxide type;
-
.8 if located in control stations and other spaces
containing electrical or electronic equipment or appliances necessary
for the safety of the craft, be provided with extinguishing media
which are neither electrically conductive nor harmful to the equipment
and appliances;
-
.9 be ready for use and located in easily visible
places such that it can be reached quickly and easily at any time
in the event of a fire;
-
.10 be located such that its serviceability is
not impaired by the weather, vibration or other external factors;
and
-
.11 be provided with a device to identify whether
it has been used.
7.7.5 Fire pumps, fire mains,
hydrants and hoses
Fire pumps, and appropriate associated equipment, or alternative
effective fire-extinguishing systems shall be fitted as follows:
-
.1 At least two pumps powered by independent sources
of power shall be arranged. Each pump shall have at least two-thirds
the capacity of a bilge pump as determined by 10.3.5 and 10.3.6 but not less than 25 m3/h. Each
fire pump shall be able to deliver sufficient quantity and pressure
of water to simultaneously operate the hydrants as required by .4.
-
.2 The arrangement of the pumps shall be such
that in the event of a fire in any one compartment, all the fire pumps
will not be put out of action.
-
.3 Isolating valves to separate the section of
the fire main within the machinery space containing the main fire
pump or pumps from the rest of the fire main shall be fitted in an
easily accessible and tenable position outside the machinery spaces.
The fire main shall be so arranged that when the isolating valves
are shut all the hydrants on the craft, except those in the machinery
space referred to above, can be supplied with water by a fire pump
not located in this machinery space through pipes which do not enter
this space. The fire main shall be capable of being drained and shall
be fitted with valves arranged so that fire main branches can be isolated
when the main is used for purposes other than fire-fighting. The spindles
of manually operated valves shall be easily accessible and all valves
shall be clearly marked.
-
.4 Hydrants shall be so arranged so that any location
on the craft can be reached by the water jets from two fire hoses
from two different hydrants, one of the jets being from a single length
of hose. Ro-ro spaces hydrants shall be located so that any location
within the space can be reached by two water jets from two different
hydrants, each jet being supplied from a single length of hose. One
hydrant shall be located in the vicinity of and outside each entrance
to a machinery space.
-
.5 Each fire hose shall be of non-perishable material.
Fire hoses shall have a length of:
-
.6 Each fire hose shall be provided with a nozzle
of an approved dual purpose type (i.e. spray/jet type) incorporating
a shutoff.
7.7.6 Protection of deep-fat
cooking equipment
Where deep-fat cooking equipment is installed, all such
installations shall be fitted with:
-
.1 an automatic or manual fixed extinguishing
system tested to an appropriate standard acceptable to the Organization;footnote
-
.2 a primary and back up thermostat with an alarm
to alert the operator in the event of failure of either thermostat;
-
.3 arrangements for automatically shutting off
the electrical power to the deep-fat cooking equipment upon activation
of the extinguishing system;
-
.4 an alarm for indicating operation of the extinguishing
system in the galley where the equipment is installed; and
-
.5 controls for manual operation of the fire-extinguishing
system which are clearly labelled for ready use by the crew.
|