7.4 Structural fire protection
7.4.1 Main structure
7.4.1.1 The requirements below apply to all craft
irrespective of construction material. The structural fire protection
times for separating bulkheads and decks shall be in accordance with tables 7.4-1 and 7.4-2, and the structural fire protection
times are all based on providing protection for a period of 60 min
as referred to in 4.8.1. If any other
lesser structural fire protection time is determined for category
A craft and cargo craft by 4.8.1,
then the times given below in 7.4.2.2
and 7.4.2.3 may be amended pro rata. In no case shall the structural
fire protection time be less than 30 min.
7.4.1.2 In using tables
7.4-1 and 7.4-2, it
shall be noted that the title of each category is intended to be typical
rather than restricted. For determining the appropriate fire integrity
standards to be applied to boundaries between adjacent spaces, where
there is doubt as to their classification for the purpose of this
section, they shall be treated as spaces within the relevant category
having the most stringent boundary requirement.
7.4.1.3 The hull, superstructure, structural bulkheads,
decks, deckhouses and pillars shall be constructed of approved non-combustible
materials having adequate structural properties. The use of other
fire-restricting materials may be permitted provided the requirements
of this chapter are complied with and the materials are in compliance
with the Fire Test Procedures Code.
7.4.1.4 7.4.1.3 does not apply to appendages such
as air propellers, air ducts to propellers, transmission shafts, rudders
and other control surfaces, struts, spars, flexible skirts, etc.,
which do not comprise part of the main structure of the craft.
Table 7.4-1 Structural fire protection times for separating bulkheads and decks of
passenger craft
Table 7.4-2 Structural fire protection times for separating bulkheads and decks of
cargo
Notes:
The figures on either side of the diagonal line represent the required
structural fire protection time for the protection system on the relevant side of the
division. When steel construction is used and two different structural fire
protection times are required for a division in the table, only the greater one need
be applied.
1
The upper side of decks within spaces protected by fixed fire-extinguishing
systems need not be insulated.
2
Where adjacent spaces are in the same alphabetical category and a note 2
appears, a bulkhead or deck between such spaces need not be fitted if deemed
unnecessary by the Administration. For example, a bulkhead need not be required
between two store-rooms. A bulkhead, is however, required between a machinery space
and a special category space even through both spaces are in the same category.
3
No structural fire protection requirements; however, a smoke-tight division made
of non-combustible or fire restricting material is required.
4
Control stations which are also auxiliary machinery spaces shall be provided
with 30 min structural fire protection.
5
There are no special requirements for material or integrity of boundaries where
only a dash appears in the tables.
6
The fire protection time is 0 min and the time for prevention of passage of
smoke and flame is 30 min as determined by the first 30 min of the standard fire
test.
7
Fire resisting divisions need not comply with 7.2.1.5.
8
When steel construction is used, fire resisting divisions adjacent to void
spaces need not comply with 7.2.1.5.
9
The fire protection time may be reduced to 0 min for those parts of open ro-ro
spaces which are not essential parts of the craft's main load bearing structure,
where passengers have no access to them and the crew need not have access to them
during any emergency.
10
On category A craft, this value may be reduced to 0 min where the craft is
provided with only a single public space (excluding lavatories) protected by a
sprinkler system and adjacent to the operating compartment.
7.4.2 Fire-resisting divisions
7.4.2.1 Areas of major and moderate fire hazard
shall be enclosed by fire-resisting divisions complying with the requirements
of 7.2.1 except where the omission
of any such division would not affect the safety of the craft. These
requirements need not apply to those parts of the structure in contact
with water at least 300 mm below the craft's waterline in the lightweight
condition in displacement mode, but due regard shall be given to the
effect of temperature of hull in contact with water and heat transfer
from any uninsulated structure in contact with water to insulated
structure above the water.
7.4.2.2 Fire-resisting bulkheads and decks shall
be constructed to resist exposure to the standard fire test for a
period of 30 minutes for areas of moderate fire hazard and 60 minutes
for areas of major fire hazard except as provided in 7.4.1.1.
7.4.2.3 Main load-carrying structures within areas
of major fire hazard and areas of moderate fire hazard and structures
supporting control stations shall be arranged to distribute load such
that there will be no collapse of the construction of the hull and
superstructure when it is exposed to fire for the appropriate fire
protection time. The load-carrying structure shall also comply with
the requirements of 7.4.2.4 and 7.4.2.5.
7.4.2.4 If the structures specified in 7.4.2.3
are made of aluminium alloy their installation shall be such that
the temperature of the core does not rise more than 200°C above
the ambient temperature in accordance with the times in 7.4.1.1 and 7.4.2.2.
7.4.2.5 If the structures specified in 7.4.2.3
are made of combustible material, their insulation shall be such that
their temperatures will not rise to a level where deterioration of
the construction will occur during the exposure to the standard fire
test in accordance with the Fire Test Procedures Code to such an extent
that the load-carrying capability, in accordance with the times in 7.4.1.1 and 7.4.2.3, will be impaired.
7.4.2.6 The construction of all doors, and door
frames in fire-resisting divisions, with the means of securing them
when closed, shall provide resistance to fire as well as to the passage
of smoke and flame equivalent to that of the bulkheads in which they
are situated. Watertight doors of steel need not be insulated. Also,
where a fire-resisting division is penetrated by pipes, ducts, electrical
cables etc., arrangements shall be made to ensure that the fire-resisting
integrity of the division is not impaired, and necessary testing shall
be carried out in accordance with the Fire Test Procedures Code. Where
machinery shafts penetrate fire-resisting watertight divisions, arrangements
shall be made to ensure that the required watertight and fire-resisting
integrity of the division is not impaired.
7.4.2.7 Ventilation openings may be accepted in
entrance doors to public toilets, provided they are positioned in
the lower portion of the door and fitted with closable grilles made
of non-combustible or fire-restricting material and operable from
outside the space.
7.4.3 Restricted use of combustible
materials
7.4.3.1 All separating divisions, ceilings or
linings, if not a fire resisting division, shall be of non-combustible
or fire restricting materials. Draught stops shall be of non-combustible
or fire-restricting material.
7.4.3.2 Where insulation is installed in areas
in which it could come into contact with any flammable fluids or their
vapours, its surface shall be impermeable to such flammable fluids
of vapours. The fire insulation in such spaces may be covered by metal
sheets (not perforated) or by vapour proof glass cloth sealed at joints.
7.4.3.3 Furniture and furnishings in public spaces
and crew accommodation shall comply with the following standards:footnote
-
.1 all case furniture, e.g., desks, wardrobes,
dressing tables, bureaux and dressers, is constructed entirely of
approved non-combustible or fire-restricting materials, except that
a combustible veneer with a calorific value not exceeding 45 MJ/m2 may
be used on the exposed surface of such articles;
-
.2 all other furniture, such as chairs, sofas
and tables, is constructed with frames of non-combustible or fire-restricting
materials;
-
.3 all draperies, curtains and other suspended
textile materials have qualities of resistance to the propagation
of flame, this being determined in accordance with the Fire Test Procedures
Code;
-
.4 all upholstered furniture has qualities of
resistance to the ignition and propagation of flame, this being determined
in accordance with the Fire Test Procedures Code;
-
.5 all bedding components have qualities of resistance
to the ignition and propagation of flame, this being determined in
accordance with the Fire Test Procedures Code; and
-
.6 all deck finish materials comply with the Fire
Test Procedures Code.
7.4.3.4 Subject to 7.4.3.5 the following surfaces
shall, as a minimum standard, be constructed of materials having low
flame-spread characteristics:
-
.1 exposed surfaces in corridors and stairway
enclosures, and of bulkheads (including windows), wall and ceiling
linings in all public spaces, crew accommodation, service spaces,
control stations and internal assembly and evacuation stations;
-
.2 surfaces in concealed or inaccessible spaces
in corridors and stairway enclosures, public spaces, crew accommodation,
service spaces, control stations and internal assembly and evacuation
stations.
7.4.3.5 7.4.3.4 does not apply to partitions,
windows and sidescuttles made of glass which are deemed to be non-combustible
and to comply with the requirements for low-flame spread surfaces
or to items and materials referred to in 7.4.3.3.footnote.
7.4.3.6 Any thermal and acoustic insulation shall
be of non-combustible or of fire-restricting material. Vapour barriers
and adhesives used in conjunction with insulation, as well as insulation
of pipe fittings for cold service systems need not be non-combustible
or fire-restricting, but they shall be kept to the minimum quantity
practicable and their exposed surfaces shall have low flame spread
characteristics.
7.4.3.7 Exposed surfaces in corridors and stairway
enclosures, and of bulkheads (including windows), wall and ceiling
linings, in all public spaces, crew accommodation, service spaces,
control stations and internal assembly and evacuation stations shall
be constructed of materials which, when exposed to fire, are not capable
of producing excessive quantities of smoke or toxic products, this
being determined in accordance with the Fire Test Procedures Code.
7.4.3.8 Void compartments, where low-density combustible
materials are used to provide buoyancy, shall be protected from adjacent
fire hazard areas by fire-resisting divisions, in accordance with tables 7.4-1 and 7.4-2. Also, the space and closures
to it shall be gastight but it shall be ventilated to atmosphere.
7.4.3.9 In compartments where smoking is allowed,
suitable non-combustible ash containers shall be provided. In compartments
where smoking is not allowed, adequate notices shall be displayed.
7.4.3.10 The exhaust gas pipes shall be arranged
so that the risk of fire is kept to a minimum. To this effect, the
exhaust system shall be insulated and all compartments and structures
which are contiguous with the exhaust system, or those which may be
affected by increased temperatures caused by waste gases in normal
operation or in an emergency, shall be constructed of non-combustible
material or be shielded and insulated with non-combustible material
to protect from high temperatures.
7.4.3.11 The design and arrangement of the exhaust
manifolds or pipes shall be such as to ensure the safe discharge of
exhaust gases.
7.4.4 Arrangement
7.4.4.1 Internal stairways connecting only two
decks need only be enclosed at one deck by means of divisions and
self-closing doors having the structural fire protection time as required
by tables 7.4-1 and 7.4-2 for divisions separating those
areas which each stairway serves.
7.4.4.2 Open stairways may be fitted in public
spaces consisting of only two decks, provided the stairways lie wholly
within such public spaces and the following conditions are met:
-
.1 all levels are used for the same purpose;
-
.2 the area of the opening between the lower and
upper parts of the space is at least 10% of the deck area between
the upper and lower parts of the space;
-
.3 the design is such that persons within the
space should be generally aware, or could easily be made aware of,
a developing fire or other hazardous situation located within that
space;
-
.4 sufficient means of escape are provided from
both levels of the space directly leading to an adjacent safe area
or compartment; and
-
.5 the whole space is served by one section of
the sprinkler system.
7.4.4.3 Lift trunks shall be so fitted as to prevent
the passage of smoke and flame from one deck to another and shall
be provided with means of closing so as to permit the control of draught
and smoke.
7.4.4.4 In public spaces, crew accommodation,
service spaces, control stations, corridors and stairways, air spaces
enclosed behind ceilings, panelling or linings shall be suitably divided
by close-fitting draught stops not more than 14 m apart. Draught stops
are not required in public spaces of category A craft having only
one public space and on other craft in spaces with open ceilings (perforated
ceilings) where the opening is 40% or more and the ceiling is arranged
in such a way that a fire behind the ceiling can be easily seen and
extinguished.
|