7.9.1 There shall be permanently exhibited, for
the guidance of the master and officers of the craft, fire control
plans showing clearly for each deck the following positions: the control
stations, the sections of the craft which are enclosed by fire-resisting
divisions together with particulars of the fire alarms, fire-detection
systems, the sprinkler installations, the fixed and portable fire-extinguishing
appliances, the means of access to the various compartments and decks
in the craft, the ventilating system (including particulars of the
master fan controls, the positions of dampers and identification numbers
of the ventilating fans serving each section of the craft), the location
of the international shore connection, if fitted, and the position
of all means of control referred to in 7.5.3, 7.6.2, 7.7.1 and 7.7.3.1. The text of such plansfootnote shall be in the official language of the flag
State. However, if the language is not English, French or Spanish,
a translation into one of those languages shall be included.
7.9.2 A duplicate set of fire control plans or
a booklet containing such plans shall be permanently stored in a prominently
marked weathertight enclosure outside the deckhouse for the assistance
of shore-side fire-fighting personnel.
7.9.3
Openings in fire resisting divisions
7.9.3.1 Except for any hatches between cargo,
special category, ro-ro, store, and baggage spaces and between such
spaces and the weather decks, all openings shall be provided with
permanently attached means of closing which shall be at least as effective
for resisting fires as the divisions in which they are fitted.
7.9.3.2 It shall be possible for each door to
be opened and closed from each side of the bulkhead by one person
only.
7.9.3.3 Fire doors bounding areas of major fire
hazard and stairway enclosures shall satisfy the following requirements:
-
.1 The doors shall be self-closing and be capable
of closing with an angle of inclination of up to 3.5° opposing
closure. The approximate time of closure for hinged fire doors shall
be no more than 40 s and no less than 10 s from the beginning of their
movement with the craft in the upright position. The approximate uniform
rate of closure for sliding fire doors shall be of no more than 0.2
m/s and no less than 0.1 m/s with the craft in the upright position.
-
.2 Remote-released sliding or power-operated doors
shall be equipped with an alarm that sounds at least 5 s but no more
than 10 s after the door is released from the continuously manned
control station and before the door begins to move, and continue sounding
until the door is completely closed. Doors designed to reopen upon
contacting an object in their paths shall re-open no more than 1 m
from the point of contact.
-
.3 All doors shall be capable of remote release
from a continuously manned central control station, either simultaneously
or in groups, and shall be capable of release also individually from
a position at both sides of the door. Indication shall be provided
at the fire door indicator panel in the continuously manned control
station whether each of the remote released doors is closed. The release
mechanism shall be so designed that the door will automatically close
in the event of disruption of the control system or main source of
electrical power. Release switches shall have an on-off function to
prevent automatic resetting of the system. Hold-back hooks not subject
to continuously manned control station release shall be prohibited.
-
.4 A door closed remotely from the continuously
manned control station shall be capable of being re-opened at both
sides of the door by local control. After such local opening, the
door shall automatically close again.
-
.5 Local power accumulators for power-operated
doors shall be provided in the immediate vicinity of the doors to
enable the doors to be operated after disruption of the control system
or main source of electric power at least ten times (fully opened
and closed) using the local controls.
-
.6 Disruption at one door of the control system
or main source of electric power shall not impair the safe functioning
of the other doors.
-
.7 Double-leaf doors equipped with a latch necessary
to their fire integrity shall have a latch that is automatically activated
by the operation of the doors when released by the system.
-
.8 Doors giving direct access to special category
spaces which are power-operated and automatically closed need not
be equipped with alarms and remote-release mechanisms required in
.2 and .3.
-
.9 The components of the local control system
shall be accessible for maintenance and adjusting.
-
.10 Power-operated doors shall be provided with
a control system of an approved type which shall be able to operate
in case of fire, this being determined in accordance with the Fire
Test Procedures Code. This system shall satisfy the following requirements:
-
.1 the control system shall be able to operate
at a temperature of at least 200°C for at least 60 minutes, served
by the power supply;
-
.2 the power supply for all other doors not subject
to fire shall not be impaired; and
-
.3 at temperatures exceeding 200°C the control
system shall be automatically isolated from the power supply and shall
be capable of keeping the door closed up to at least 945°C.
7.9.3.4 The requirements for integrity of fire-resisting
divisions of the outer boundaries facing open spacesfootnote of a craft shall not apply to glass partitions,
windows and side scuttles. Similarly, the requirements for integrity
of fire-resisting divisions facing open spaces shall not apply to
exterior doors in superstructures and deck houses.
7.9.3.5 Doors in smoke-tight divisions shall be
self-closing. Doors which are normally kept open shall close automatically
or by remote control from a continuously manned control station.